Connecting The Room Thermostat; Connecting The External Probe; Gas Valve; Gasconversion - Westen quasar E 24 F Manual Para El Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62

11.1 CONNECTING THE ROOM THERMOSTAT

To connect the Room Thermostat to the boiler, proceed as follows:
• access the power terminal block as described in the ELECTRICAL CONNECTIONS section;
• remove the jumper on terminals (1) and (2);
• thread the two-wire cable through the grommet and connect it to these two terminals.

11.2 CONNECTING THE EXTERNAL PROBE

To connect the External Probe, supplied as an accessory, to the boiler, proceed as follows:
• access the power terminal block as described in the ELECTRICAL CONNECTIONS section;
• connect the external probe to the two RED wires fitted with faston covers;
• with the external probe connected, select the "kt" climate curve by pressing
see the curves chart in "SECTION" E at the end of this manual (the preset curve is 0).
KEY TO CURVE CHART Kt - "SECTION" E
Flow temp

12. GAS VALVE

12.1 GASCONVERSION

The Technical Assistance Service can convert this boiler to natural gas (G20) or LPG (G31). Carry out the following operations:
A) replace the main burner injectors;
B) parameterise the electronic board;
C) mechanically calibrate the gas valve pressure regulator;
D) electronically calibrate the gas valve;
E) final checks.
Parameter
F02
F08
F18
F45
F48
F64
Outside temp
24 F
G20
G31
0
55
60
, selecting from the available ones (0...90),
G20
1
0
100
18
1
100
1
31
18 F
G31
1
100
7113156.01 (1-05/13)

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Quasar e 18 f

Tabla de contenido