Operation
Figure 2C - Control Panel (CSA Models)
2
3
Figure 3 - Generator Controls
17
18
6
5
11
15
Figure 4 - Generator Controls
6
1
19
9A
20
16
2.2 HOURMETER
The Hourmeter tracks hours of operation for scheduled maintenance
(Figure 5):
There will be a "CHG OIL" message every 100 hours. The message
will flash one hour before and one hour after each 100 hour
interval, providing a two hour window to perform service.
This message will actually begin flashing at 99 hours and disable
itself at 101 hours again, providing a two hour window to perform
the service.
Every 200 hours the "SVC" icon on the lower left hand corner of
the display will flash. The message will flash one hour before and
one hour after each 200 hour interval providing a two hour window
to perform service.
Figure 5 – Hourmeter
0000.0
HOUR GLASS
GRAPHIC
When the hour meter is in the Flash Alert mode, the maintenance
message will always alternate with elapsed time in hours and
tenths. The hours will flash four times, then alternate with the
maintenance message four times until the meter resets itself.
• 100 hours - CHG OIL — Oil Change Interval (Every 100 hrs)
• 200 hours - SVC — Service Air Filter (Every 200 hrs)
The hour glass graphic will flash on and off when the engine
is running. This signifies that the meter is tracking hours of
operation.
2.3 CONNECTION PLUGS
2.3.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 20 Amp
push-to-reset circuit breaker (Figure 6). Use each socket to power
120 Volt AC, single phase, 60 Hz electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 Amps of current. Use only
high quality, well-insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably less than
15 feet long, to prevent voltage drop and possible overheating of
wires.