Carrier 80HMA Manual De Instalación página 28

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 137
Variable table
Nr.
Name
Par.
Zone for which variable table is
Virtual zone
22
showed, at the board selected
selection
(Par. 127 board address)
Displays the Flow Switch status:
Flow Switch
31
0. Water not flowing
Status
1. Water Flowing
Displays the Pressure Switch
Pressure
status:
32
Switch Status
0. No pressure
1. Pressure
Force the system to work in
these mode for installation:
0. No forced mode
4. Booster Heat: heating at the
33
Forced Mode
maximum power
5. Booster Cool: cooling at the
maximum power
6. Rating Heat: only for testing
7. Rating Cool: only for testing
It shows and change the main
mode of the system:
0. Off
34
System Mode
1. Sanitary
2. Cooling
3. Heating
It shows the chiller mode:
0. Off
1. N.A.
2. Cool
3. Heat
4. Booster Heat
Heat pump
5. Booster Cool
35
mode
6. Rating Heat
7. Rating Cool
8. Freeze protection
9. Defrost
10. Hi Temp Protection
11. Timeguard
12. Fail
Use Days button to select
the sub-parameter (when
available). Show the
temperature of:
Refrigerant expansion
temperature (°C)
Outdoor temperature read
from heat pump (°C)
Heat pump coil temperature (°C)
Heat pump
36
Refrigerant compressor
temperatures
suction temperature (°C)
Refrigerant compressor
discharge temperature (°C)
Heat pump leaving water
temperature (°C)
Heat pump entering water
temperature (°C)
Heat pump refrigerant
temperature (°C)
16 80HMA
Description
Master
LEVEL 3
Reading
x
x
x
x
x
Available on
User
Heat
Slave Pool
Interface
Pump
x
x
x
x
x
x
RANGE
MIN
MAX DEFAULT
Own
1
2
zone
x
-
-
-
x
-
-
0
7
0
-
-
-
x
-
-
-
x
-
-
-

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido