Variable table
Nr.
Name
Par.
Heating
Selection of Heat climatic curve:
Climatic Curve
0. User define climatic curve
51
nr. (see pic.
1 - 6. See manual for climatic
5A)
curve details
Heating
User define heating climatic
Climatic Curve
52
curve: minimum ambient
Point A
outdoor temperature (°C)
(see pic. 6)
Heating
User define heating climatic
Climatic Curve
53
curve: maximum ambient
Point B
outdoor temperature (°C)
(see pic. 6)
Heating
User define heating climatic
Climatic Curve
54
curve: water setpoint at Par. 53
Point D
value (°C)
(see pic. 6)
Heating
User define heating climatic
Climatic Curve
55
curve: water setpoint at Par. 52
Point C (see
value (°C)
pic. 6)
Cooling
Selection of Cool climatic curve:
Climatic Curve
0. User define climatic curve
56
nr. (see pic.
1 - 2. See manual for climatic
5B)
curve details
Cooling
User define cooling climatic
Climatic Curve
57
curve: maximum ambient
Point B (see
outdoor temperature (°C)
pic. 6)
Cooling
User define cooling climatic
Climatic Curve
58
curve: minimim ambient
Point A (see
outdoor temperature (°C)
pic. 6)
Cooling
User define cooling climatic
Climatic Curve
59
curve: water setpoint at Par. 57
Point D (see
value (°C)
pic. 6)
Cooling
User define cooling climatic
Climatic Curve
60
curve: water setpoint at Par. 58
Point C (see
value (°C)
pic. 6)
When Eco is Active (°C):
In Cooling mode increase the
Delta
water setpoint temperature by
Temperature
61
this value
for Room ECO
In Heating mode descrease the
mode
water setpoint temperature by
this value
18 80HMA
Description
Master
Climatic curve
x
x
x
x
x
x
x
x
x
x
x
Available on
User
Heat
Slave Pool
Interface
Pump
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
RANGE
MIN
MAX DEFAULT
0
6
0
-20
15
-7
10
50
20
20
60
20
20
80
35
0
2
0
24
46
40
0
30
22
4
20
12
4
20
18
0
10
5

Hide quick links: