Relevador Remoto Supervisado - DMP XR200 Guia De Instalacion

Tabla de contenido

Publicidad

DIAGRAMAS DEL SISTEMA

25.6 Relevador remoto Supervisado

J3
Answering Machine
Bypass Relay
Use Model 305
AC
AC
1
2
DPDT Relay
Use Model ASRB-1 from Advanced
Signaling. 30mA coil operating
current at 12 VDC.
Normally Open
Normally Closed
contacts will
close on alarm.
Open on alarm.
Remote DPDT
Relay
10K EOL Resistor
DMP Model 308
Wiring between the 866 Module
and the DPDT Relay is supervised
against open, shorts, and grounds.
Any of these trouble conditions will
cause the 866 Module's Bell
Trouble contacts to open.
Notification Circuit Module
DMP Model 866
45mA @12 VDC
Normal/Silence Switch
866
Module
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Digital Monitoring Products
30
J12
J11
XR200 Command Processor™ Panel
J4
DD, MPX
Tamper
Selection
Header
Headers
Ground Start Relay
J2 Output Header
K2 K4
Use Model 305
All outputs must be located
within the same room as
the control panel.
J10
Relay Output 1
Use Model 305
+B
-B
BELL GND
RED YEL GRN BLK
SMK GND
3
4
5
6
7
8
9
10
11
S
S
contacts will
DMP Part #DI-001 Rectifier (1N4001
diode) in series with input from Model
866 Module terminal 6.
The 866 Module must be
installed in the panel enclosure
or in a 340FC, 349, or 350
Enclosure connected by no more
than 20 feet of conduit.
1K EOL
J2 Output Header
Relay Output 2
K6 K7
Use Model 305
Z1
GND
Z2
Z3
GND
Z4
Z5
GND
Z6
12
13
14
15
16
17
18
19
20
21
S = Supervised Circuit
Model 430
Output Harness
J16
Panel
Reset
Z7
GND
Z8 Z9+ Z9- Z10+ Z10-
22
23
24
25
26
27
28
S
S
The zone connected to
the Bell Trouble contacts
on the 866 Notification
Circuit Module must be
programmed as a
Supervisory Type zone
and selecetd for display
in the Status List. See
the XR200 Programming
Guide
(LT-0196).