2. Mounting of the enclosure
The RAYSTAT-ECO-10 can be installed indoor or outdoor.
Do not install the thermostat under the thermal insulation.
A.
Wall mounting
Mount the enclosure using wall fasteners (screws) via the four, 4
mm Ø holes.
B.
Mounting on a pipe
Thermal Management offers different support brackets
(not included) to mount the RAYSTAT-ECO-10 on a pipe: SB-100
or SB-101.
3. Wiring
Remove the terminal protection cover to access the terminals.
Power cable
Enter a single phase (230 Vac.) power cable through the M25 gland 2
(see drawing A ) and wire according to the wiring diagram (page 33).
Wiring the heating cable can be done either:
A.
Via junction box or contactor or when using RayClic with the cold
cable through the M25 gland 3 .
B.
Directly into RAYSTAT-ECO-10.
In this case, the M25 gland 3 , which is delivered pre-mounted to
the RAYSTAT-ECO-10, is to be replaced by an appropriate kit.
Follow instructions supplied with the kit for installation.
Important: For Voltage Free Operation, the wire links (W1) and (W2) need
to be removed. Failure to remove the wire links can result in damage to
the unit or to other connected equipment. Wiring of RAYSTAT-ECO-10
to a remote alarm is optional through the M20 gland 4 . Thermal
Management strongly recommends the use of a remote alarm for critical
operations (e.g. when extreme low temperatures (lower than –25°C) can
be expected or for critical processes).