Multicheck6010
The following menu is displayed:
After re-activating the RCD, the autotest sequence automatically proceeds with step 2.
2. The following steps are indicated below:
• Trip-out time measurement a test current of IΔN, started with the negative half-wave at
180º. Measurement normally trips an RCD.
• Trip-out time measurement with a test current of 5x IΔN, started with the positive half-
wave at 0º. Measurement normally trips an RCD within allowed time period.
• Trip-out time measurement with a test current of 5x IΔN, started with the negative half-
wave at 180º. Measurement normally trips an RCD within allowed time period.
• Trip-out time measurement with a test current of ½x IΔN, started with the positive half-
wave at 0º. Measurement does not normally trip an RCD.
• Trip-out time measurement with a test current of ½x IΔN, started with the negative half-
wave at 180º. Measurement does not normally trip an RCD.
• Ramp test measurement with a test current started with the positive half-wave at 0º.
This measurement determine the minimum current required to trip the RCD.
• Ramp test measurement with a test current started with the negative half-wave at
180º. This measurement determine the minimum current required to trip the RCD.
In those measurement when the RCD is tripped, it is necessary to re-activate it before
the autotest sequence automatically proceeds with the next step.
The final menu is displayed:
Figure 4 19: Step 1 RCD autotest results
Figure 4 20: Step 8 RCD autotest results