Technical Data - Cooper Crouse-Hinds CEAG PX 04 Serie Instrucciones De Uso

Proyectores de lámparas de bulbo en atmósferas explosivas
Ocultar thumbs Ver también para CEAG PX 04 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Safety Instructions
For skilled electricians and instructed
personel in accordance with national
regulation, including the relevant standard
and, where applicable, in acc. with
IEC 60079-17 on electrical apparatus for
explosive atmospheres.
The floodlights must not be operated in Zone 0
or 20!
The light fitting must not be use while excessive
deposit of dust (≥ 50 mm, accd. EN 50281-1-2)
exist.
The technical data indicated on the floodlights
are to be observed!
Changes of the design and modifications to
the floodlights are not permitted!
The floodlights shall be operated as intended
and only in undamaged and perfect
conditions!
Only genuine Cooper Crouse-Hinds, S.A
spare parts may be used for replacement!
Repairs that affect the explosion protection,
may only be carried out by Cooper Crouse-
Hinds, S.A. or a qualified "electrician"!
Do not keep these operating instructions inside
the floodlights during opertion.
The national safety rules and regulations for
prevention of accidents and the following
safety instructions which are marked with an
(
) in theses operting instructions, will have
to be observed!
2. Conformity with standards
This explosion protected floodlights meets the
requeriments of EN50014, EN50018, EN50019,
and EN60598. It also complies with the
EC Directives for "Apparatus and protective
systems for use inexplosive atmospheres"
(94/9/EC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
DIN EN ISO 9001: 2000.
The luminaire are suitables for use in explosive
atmospheres, Zone 1and 2 acc. to IEC60079-10 as
well as Zone 21 and 22 acc. to EN 500281-1-1.

3. Technical data

EC type examination
certificate:
PTB 04 ATEX 1046
Category of application:
II 2G EEx d/de IIB T4-T2
II 2D IP 6X T85°C - 210 °C
Serie of types:
See Table 1
Lamps to be use:
See Table 1
Approval of the production
Quality assurance:
LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 66/67
Insulation class
acc. EN60598:
I
Temperature of use:
-20
C a + 40
o
>40
C a + 55
o
Rated voltage:
See Table 1
Material of enclosure:
Metal aloy aluminium
without Cu,
painted polyester grey.
Material of glas
Borosilicate
Storage temperature in original
Packing
-50
C a + 60
o
Terminals capacity:
See wiring diagram
Entries of cables
Indirect entry:
2 x M25 x 1,5 ISO965-1,
one plugged
Dimensions:
See figure 3.
Notes:
3) See table 2, thermal class and surface temperature acc. the lamp used.
6 6 6 6 6
Cooper Crouse-Hinds S.A.
4. Installation
The respective national regulations as well as
the general rules of engineering which apply to
the installation and operation of explosion
protected apparatus will have to be observed!
Transport and storage of the floodlights is
permitted in original packaging only!
Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions.
Montage position
Montage position
Montage position
Montage position
Montage position
Opening and closing the floodlights
The opening of luminaire always shall be without
voltage!.
The luminaire is well closed when the
gap of the flange joints, in every side of the
enclosure are < 0.2 mm.
There are Ex-d joints between the frame and
lamp housing and between the cover and
controlgear housing!
Dimensions for mounting: See figures 3
Accesories for mounting:
See Cooper Crouse-Hinds,S.A. catalogue
Cable entries
Mounting the selected cable entries
(cable glands) acc. type and dimensions of
the main conection cable, following their
manufacturer instructions.
The cable entries devices has to be a protection
mode EExe II.
Unused cabe entries have to be closed by
a correspondance certified blanking plug.
If the original blanking plugs are used, these must
be tightened with 15 Nm torque.
Main conection: See wiring diagram.
Lamps mounting
Only must be mounting apropiated lamps for the
supplied luminaire. See indications in the general
label of the luminaire and in this instructions!
5. Taking into operation
Prior to operation check the floodlights for its
Prior to operation check the floodlights for its
Prior to operation check the floodlights for its
Prior to operation check the floodlights for its
Prior to operation check the floodlights for its
3)
proper funtioning and installation in compliance
proper funtioning and installation in compliance
proper funtioning and installation in compliance
proper funtioning and installation in compliance
proper funtioning and installation in compliance
3)
with these operting instructions and others
with these operting instructions and others
with these operting instructions and others
with these operting instructions and others
with these operting instructions and others
applicable regulations!
applicable regulations!
applicable regulations!
applicable regulations!
applicable regulations!
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
between PE and N.
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
C
o
6. Maintenance
C
o
Observe the national regulations applicable to the
maintenance, servicing and test of apparatus for
explosive atmospheres e.g
IEC 60079-17 as well as the general rules of
engineering!
C
o
Servicing
The responsable of the safe use of these
The responsable of the safe use of these
The responsable of the safe use of these
The responsable of the safe use of these
The responsable of the safe use of these
apparatus is the property of the user!
apparatus is the property of the user!
apparatus is the property of the user!
apparatus is the property of the user!
apparatus is the property of the user!
When servicing, in particular those components that
affect the explosion protection, , , , , will have to checked,
e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greased.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminals for their firm fit.
Lamp replacement: Keep replacement intervals
as specified by the lamp manufacturer!
Type of lamps used in acc. with the luminaire
specifications.
The flameproof gap of these apparatus have
to be greased permanentlly in order to ensure it's
protection in front of the corrosion, water ingrees
and size-up problems.
Cleaning the rests of grease and corrosion do not
use sharp metallic devices who can damage the
surface of the joint, and greasing they using
apropiate greasse therminally and chemically
stable with a drop point > 200 ºC like e.g.:
GRASEX from Cooper Crouse-Hinds, S.A.!.
When the housing need to be repeinted, pay
attention that the flameproof joints rest without
any part with coating!.
Less for PTFE coating, that in this case ask
Cooper Crouse-Hinds, S.A. for the correct process!
Inspection
The nationals regulations have to be observed!
The nationals regulations have to be observed!
The nationals regulations have to be observed!
The nationals regulations have to be observed!
The nationals regulations have to be observed!
I.e. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical Low
Votage Regulation following the indications stablished
in IEC 60079-17.
When the inspections are in degree of "Detailled"
or "Closed", the luminaires have to be
disconnected from the main conection!.
Repairing
The nationals regulations have to be observed.The
tasks of repairing have to be made by "qualified"
personnel!.
The reparation of the sealed part between
the collarand the glass have to be done
by Cooper Crouse-Hinds. The users are not
authorized to repair this sealed part.
All reparations have to be done without
For repair electrical equipments in protection mode is
suggested follow the instructions indicated
in IEC 60079-19.
Only use genuine Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cooper Crouse-Hinds
Cooper Crouse-Hinds
S.A.
S.A. spare parts!.
S.A.
S.A.
S.A.
Subject to alteration or supplement of this product
without any advertisement before.