ICAR by ORTEA NEXT
6
KEYPAD LOCK
A function to exclude all modification to operating parameters can be enabled; measurement viewing is still provided in any
case. To lock and unlock the keypad, press and keep the
twice and after that release
the lock is enabled, it is not possible to make the following operations:
Operation between automatic and manual mode
Access to set-up menus
Change of cos set-point
By attempting to conduct the above operations, the display will view
7
EXPANDABILITY
Thanks to expansion bus, the RPC 5LGA can be expanded with one expansion series module.
The supported expansion modules can be grouped in the following categories:
additional steps
communication modules
digital I/O modules
To insert an expansion module:
remove the power supply to RPC 5LGA regulator.
remove the protecting cover of the expansion slot.
insert the upper hook of the expansion module into the fixing hole on the top of the expansion slot.
rotate down the module body, inserting the connector on the bus.
push until the bottom clip snaps into its housing.
When the RPC 5LGA regulator is powered on, it automatically recognises the expansion module that have been mounted.
The expansion modules provide additional resources that can be used through the dedicated setup menus.
The setup menus related to the expansions are always accessible, even if the expansion modules are not physically fitted.
The following table indicates which models of expansion modules are supported:
8
IR PROGRAMMING PORT
The parameters of the RPC 5LGA regulator can be configured through the front optical port, using the IR-USB code
A25060046580008 programming dongle, or with the IR-WiFi code A25060046580009 dongle. This programming port has
the following advantages:
Allows for configuring and servicing the RPC 5LGA regulator without having to access the rear of the device or having
to open the electrical panel.
It is galvanically isolated from the internal circuits of the RPC 5LGA regulator, guaranteeing the greatest safety for the
operator.
High speed data transfer.
IP54 front panel protection.
Limits the possibility of unauthorized access with device configuration since it is necessary to have the IR-USB or IR-
WI-FI dongles.
Simply hold the dongle up to the front panel, connecting the plugs to the relevant connectors, and the device will be
acknowledged as shown by the LINK LED on the programming dongle flashing green.
USB programming dongle code A25060046580008
9
PARAMETER SETTING VIA PC
The PFC Remote monitoring software can be used to transfer (previously programmed) set-up parameters from the RPC
5LGA regulator to the hard drive of the PC and vice versa. The parameter may be partially transferred from the PC to the
RPC 5LGA regulator, transferring only the parameters of the specified menus.
..The display will show
LOC
MODULE TYPE
CODE
ADDITIONAL STEPS
OUT2NO
COM232
COMMUNICATION
COM485
13 / 40
key pressed. Then press the ▲ key three times and the ▼key
when the keypad is locked and
to indicate the locked keypad state.
LOC
FUNCTION
2 STEP RELAYS'
RS-232
RS-485
WIFI programming dongle code A25060046580009
ALL75 mar19
when it is unlocked. When
UNL
CLICK!