Hayward HPE0811D Manual Do Utilizador página 22

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 24
When an alarm sounds:
The display will flash and the alarm message will appear as in the table below.
The machine will stop if necessary
Important note: any work must be done by qualified person.
The alarm is cancelled automatically when the fault is cleared
Codes
Possible Cause(s)
Water temperature measured by the
AL
probe is under the lower limit pro-
grammed into the regulator
Water temperature measured by the
AH
prove is higher than the upper limit
programmed into the regulator
S1 temperature probe disconnected
E1
or faulty
EE
Memory Error
PA
Request for access code
The heat pump
does not start up
when switched on
Low pressure fault
High pressure fault
MESSAGE FROM THE REGULATOR
Check the value entered and lower it if
Check the value entered and raise it if
Check the connection between the probe
and the regulator Replace the probe
BREAKDOWNS AND FAULTS
Check the electrical connection to the Heat pump (See wiring diagram)
For three phase Heat Pumps, check the phase controller. Reverse the phase order if necessary. Replace if faulty
Check that the HP and LP sensors are correctly connected (see wiring diagram)
Check that the HP sensor is set (press the blue button located on the HP sensor)
Check that the flow controller is in good condition and correctly connected Replace if necessary
Check that the KT start-up time delay is correctly connected (see wiring diagram) Replace if necessary.
Check that the LP sensor is in good condition and correctly connected (see wiring diagram)
Check that the fan is turning in an anti-clockwise direction when viewed from the front
The evaporator is clogged. Clean with compressed air from inside to outside the machine
Check that the HP sensor is in good condition and that it is correctly connected (see wiring diagram)
Insufficient water flow to the condenser. Reset the by-pass valve
ALARMS
Corrective Action(s)
necessary
necessary
The outside temperature is lower than — 11°C
Check that the fan is operating correctly
Possible loss of charge, check for leaks.

Comments
Access code required
Access code required
/
Reserved for the installer or other
authorised person

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hpe1011dHpe1311dHpe1611dHpe1313dHpe1613dHpe2413d

Tabla de contenido