Control Terminals; Commissioning Via The Control Unit Kp500 - BONFIGLIOLI Vectron ACTIVE Serie Guia De Inicio Rapido

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2.7

Control Terminals

Caution!
Switch off power supply before connecting or disconnecting the control inputs and outputs.
X210A
1
+20 V/180 mA
2
GND 20 V
3
S1IND
S2IND
4
5
S3IND
6
S4IND
7
S5IND
M
X210B
1
S6IND
GND 20 V
2
-
+
S1OUT
3
-
+
MFO1A
V
4
+10 V/ 4 mA
5
MFI1A
6
GND 10 V
7
X10
X10
1
2
3
Note:
The listed assignment of functions to control terminals is the factory setting in the configurations 110 and 410
Configuration
(setting of parameter
The functions can be assigned to the control terminals freely programmable.
Further configurations are listed in the operating instructions manual.
3

Commissioning via the control unit KP500

The optional control unit KP500 enables the parameterisation, parameter display and control of the frequency
inverter. It must be connected to the front of the frequency inverter.
Note:
Further methods of commissioning (e.g. via optional communication modules) are described in the operating
instructions manual on the attached CD.
06/07
06/07
X210A.1
Supply voltage +20 V
X210A.2
Ground 20 V
X210A.3
Digital input,
Controller release / error acknowledgment
X210A.4
Digital input Start of clockwise operation
X210A.5
Digital input Start of anticlockwise operation
X210A.6
Digital input Data set change-over 1
X210A.7
Digital input Data set change-over 2
X210B.1
Digital input Motor thermal contact
X210B.2
Ground 20 V
X210B.3
Digital output Operating message
X210B.4
Analog output, voltage signal proportional actual
frequency
X210B.5
Supply voltage +10 V for Reference value po-
tentiometer
X210B.6
Analog input Reference speed 0...+10 V
X210B.7
Ground 10 V
1...3
Relay output for monitoring function,
make contact: 240 VAC / 5 A, 24 VDC / 5 A,
break contact: 240 VAC / 3 A, 24 VDC / 1 A
S3OUT
30 to the value 110 or 410).
Control terminal X210A
Control terminal X210B
Control terminal X10
I
= 180 mA
max
U
= 30 V,
max
10 mA at 24 V
U
= 30 V,
max
10 mA at 24 V
U = 24 V,
I
= 40 mA
max
I
= 4 mA
max
27
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Act 201Act 401

Tabla de contenido