If the setup was changed, the message "SEtUP" is displayed again.
•
Confirm this message by pressing the ENT key in order to continue the commissioning procedure.
•
After initialization, confirm the selected configuration by pressing the ENT key.
Motor type
•
For parameter
Caution!
If the motor type is not entered correctly, the drive may be damaged.
Operation mode
0 - Unknown
1 - Asynchronous
2 - Synchronous
3 - Reluctance
10 - Transformer
Enter the machine data which is indicated on the type plate of the machine into the following parameters.
•
No.
370 Rated Voltage
371 Rated Current
372 Rated Speed
•
Use the arrow keys to select the required parameter and edit the parameter value.
Use the ENT key to confirm the selected parameter and the parameter values entered.
•
Attention!
The rated data of the motor must be entered according to the specifications on the rating plate for the motor
connection type used (star or delta connection). If the data entered deviate from the rating plate, the parameters
will not be identified correctly. Take the higher rated current in case of switching from star to delta connection of
the connected asynchronous motor into account.
After the machine data have been entered, the calculation or examination of the parameters is
started automatically. The display changes over to "CALC" for a short time. If the verification of
the machine data is successful, the guided commissioning procedure continues with the identifi-
cation of the parameters (measuring additional machine data).
The warning and error messages displayed during the verification process have to be observed.
•
To ignore the warning messages, press the ENT key. The guided commissioning is continued. However, it
−
is recommended that the data be checked and corrected if necessary.
To correct the entered parameter values after the warning or error message, press the ESC key. Use the
−
arrow keys to switch to the parameter value which is to be corrected.
While the drive is at a standstill additional machine data is measured.
The measured values are entered in the parameters automatically.
Confirm the display "PAidE" by pressing the ENT key.
•
After completion of the parameter identification, observe warning and error messages.
•
No signal is present at digital input S1IND. If a signal was already applied at the beginning of
the guided commissioning, the "S1Ind" message is not displayed.
Note:
The parameter identification feature of the frequency inverter requires the presence of a signal at digital input
S1IND for release of the power unit.
•
Confirm the final "rEAdY" message by pressing the ENT key.
Canceling the operation with the ESC key or withdrawing the release signal S1IND results in an
incomplete take-over of the values.
06/07
06/07
369 select the connected machine.
The motor is not a standard type.
Three-phase asynchronous motor, squirrel cage
Three-phase synchronous motor
Three-phase reluctance motor
Transformer with three primary windings
Description
Function
No.
Description
374
Rated Cosinus Phi
375
Rated Frequency
376
Rated Mech. Power