Analog Operation
which is proportional to an actual value.
Setting:
Motor Temp. Operation Mode.
tem. Connect a suitable sensor to digital input S6IND.
Setting:
Operation Mode
applications such as pumps and fans or after acknowledgement of an error switch-off. If synchro-
nization to the motor speed is not possible, the function is quit and a fault message is issued.
Setting:
Operation Mode
0113 (Section 5.4, 5.5), VDE 0100 Part 227 and the national regulations. Make sure that auto-
matic startup does not result in any dangerous situation.
Setting:
Operation Mode
deceleration operations, is limited by means of the voltage controller or an external braking resis-
tor in order to avoid an error switch-off due to overvoltage.
Setting:
The following parameters are displayed in addition to the basic parameters in configuration 410.
Integral Time 1
the mechanical moment of inertia, via the integral time of the speed controller. The lower the
value is, the more dynamic the behavior. The increase in inherent instability of the system is pro-
portional to the reduction of the integral time.
Setting:
Current Limit
torque is limited to the rated torque if the current limit is the same as the
the motor.
Setting:
I
U
FIN,
FIN,
instructions manual), o: overload capacity of the frequency inverter
32
32
553 - output MFO1 supplies a pulse width modulated signal (0 V ... 10 V)
7 -
actual frequency, 0 Hz ...
20 -
active current, 0 A ... I
30 -
active power P
50 -
effective current, 0 A ... I
52 -
machine voltage, 0 V ... 1000 V
570 - monitoring the motor temperature protects the drive sys-
0 -
thermo-contact switched off
1 -
thermo-contact warning message
2 -
thermo-contact error switch-off
3 -
Thermo-contact error switch-off after 1 min
4 -
Thermo-contact error switch-off after 5 min
5 -
Thermo-contact error switch-off after 10 min
645 (for synchronization) - synchronization to a rotating drive is useful in some
0 -
switched off
10 -
synchronization switched on, quick synchronization
651 - automatic startup of the drive is permissible only in accordance with VDE
0 -
switched off, control signal at S1IND, S2IND or S3IND
1 -
automatic startup, control signal at S1IND, S2IND or S3IND
670 - the DC link voltage, which increases due to generatoric operation and/or
0 -
switched off, limited by connected brake resistor
1 -
overvoltage controller, controlled deceleration ramps
722 - the control behavior of configuration 410 is to be adapted, depending on
0 ... 60000 ms
728 - the speed and torque can be controlled separately in configuration 410. The
0.0 A ... o⋅I
FIN
P
: nominal values of frequency inverter (listed in "Technical Data" in the operating
FIN
Maximum Frequency
FIN
Rated Mech. Power
, 0 kW ...
wirk
FIN
419
376
Rated Current
371 of
06/07