Lamborghini Caloreclima EM 35-E Manual Para La Instalacion Y El Mantenimento página 44

Quemadores de aire forzado para calderas normales
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

MULTIBLOC VALVE ADJUSTMENT
MB-VEF
Adjustment range
Max working pressure p
max
Max permissible working pressure at which all functions are assured.
Intake pressure range p
e
Range between minimum and maximum intake pressures that gives optimum performance.
AIR pressure p
L
Pressure generated by the fan. Air pressure influences total gas delivery rate. This pressure
is a reference value for pressure at the burner p
.
Br
GAS pressure at burner p
Br
Gas pressure measured upstream from the mixing device. Pressure measured after last
component of the train.
Average pressure p
a
Pressure at outlet from pressure regulator measured before valve V2.
Combustion chamber pressure p
F
Pressure in the combustion chamber. Combustion chamber pressure (positive or negative
pressure) may vary as it is influenced by:
- power
- dirtiness
- variation of cross-sections
- atmospheric conditions (etc.)
Combustion chamber pressure counteracts the combustion air flow. It must therefore be
considered as a disturbance factor. By adjusting the ratio to V = 1:1 this disturbance factor
becomes negligible as the pressure in the combustion chamber has an equivalent effect on
both the air and gas total delivery rates.
UK
44

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Em 40/2-eEm 40/m-e

Tabla de contenido