GF EA 11 Manual Instrucciones página 40

Actuadores eléctricos
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Technical data
Weight
Ambient temperature
Electrical connection
Overload protection
Permitted humidity
Protection class
Overvoltage category
as per DIN EN
61010-1
Height above sea level
(UL/CSA)
Degree of
contamination as per
DIN EN 61010-1
40
Electrical actuators type EA 11/ 21/ 31/ 42
EA11
EA21
1.857 kg
2.193 kg
-10° to +
-10° to + 45° C
50° C
Connector plug
3 P+E as per
Connector plug 3 P+ E as per DIN EN
EN 175301-803
175301-803
(formerly DIN
43650),
Cable screw connection M20x1.5 as per
additional
ISO 724
cable entry for
PG11
Current/time-dependent (resetting),
temperature-dependent.
Current/time-
The overload protection of the engine is
dependent
dimensioned in such a way that engine
(resetting)
and supply board are protected. As soon
as the load is in the torque range, the
actuator continues to run.
max. 80% to
31° C, reducing
in a straight
max. 90% relative humidity, non-
line to 50%
condensing
relative
humidity at 40°
C
IP65 as per EN60529, UL/CSA: use in internal rooms
IP67 as per EN60529: use of cable glands and vertical
assembly
II
< 2000m
2
EA31
EA42
3.536 kg
4.995 kg
-10° to + 50°
-10° to + 50°
C
C

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ea 21Ea 31Ea 42

Tabla de contenido