Elements Of Automatics - mundoclima MU-WING-W Manual De Instalación Y Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Recommended safety devices and wires
Device
Overload and short circuit protection
Differential current protection
Power wire cross-section
IMPORTANT! 7KH VSHFL¿FDWLRQ RI FDEOHV DQG SURWHFWLRQV UHIHUV WR XQERXQGHG DUUDQJHPHQW RI FDEOHV EDVLF H[HFXWLRQ RI WKH HOHFWULFDO LQVWDOODWLRQ DFFRUGLQJ WR WKH 31,(&  VWDQGDUG 
One should always abide by the local laws and recommendations concerning device connection.
MU-WING is equipped with a terminal strip adjusted to an appropriate thickness of wires.
MU-WING-10/6-R3
MU-WING-15/12-R3
MU-WING-20/15-R3
IMPORTANT!
It is recommended to connect wires to the terminal strip with previously clamped appropriate clip ends.
Make sure that the space around the place where the air is sucked in by the curtains, as well as around the exhaust grid, is free of any structural elements of the building, which might
KDPSHU WKH ÀRZ RI DLU HJ VXVSHQGHG FHLOLQJV FRYHULQJ GHYHORSPHQW YHQWLODWLQJ GXFWV HWF 

4. ELEMENTS OF AUTOMATICS.

(OHFWULFDO FRQQHFWLRQV FDQ EH FDUULHG RXW RQO\ E\ TXDOL¿HG HOHFWULFLDQV DFFRUGLQJ WR WKH ELQGLQJ UHJXODWLRQV RI
industrial safety;
sssembly instructions;
technical documentation for each individual element of automatics.
IMPORTANT! Study the original documentation delivered together with the elements of automatics, prior to the commencing of assembly and connecting of the system.
MODEL
DIAGRAM
IMPORTANT! If required, the conductors that belong to additional elements of control automatics (thermostat, door switch, wall-mounted controller) should be installed in separate cable
channels, out-of-parallel to the supply conductors.
MU-WING-W
1m
1,5m
C6/6kA
IDN=30mA type AC lub A
IN=16A
3x1,5mm
TECHNICAL DATA
CONTROLLER HMI
Device operation: Capacitive touch buttons
Power supply: 230 V AC
Temperature measurement: -10°C ... +99°C ; NTC10K
Outputs:
- 1 analog output 0-10V (8 bit, Imax = 20 mA)
- 2 relays outputs (250 VAC, AC1 500 VA dla 230 VAC)
Inputs: 1 digital input type "dry contact", Imax = 20 mA
Communication: Modbus RTU
Parameters of working environment: temperature:
0 - 60°C, humidity: 10 - 90%, without condensation
DOOR SENSOR (REED SWITCH)
FRQWHFW FRQ¿JXUDWLRQ 12
switching current: 500 mA
switching voltage: max 200 V
connection: screw
MU-WING-R3
2m
1m
1,5m
B16/3/6kA B20/3/6kA B25/3/6kA
IDN=30mA type AC lub A
IN=40A
2
5x1,5mm
2
5x2,5mm
MU-WING-W
MU-WING-A
used for control all types of MU-WING curtains
touch control panel
the main on / off switch (ON / OFF)
three-stage adjustable fan speed of the EC motor
built-in thermostat with possibility weekly programing
continuous mode
function of heating and ventilation
REVáXJD F]XMQLND GU]ZLRZHJR
two-stage adjustable of heating power
RS 485 with ModbusRTU
Suggested cross sections of electrical cables:
- L, N : 2x1 mm
2
- H1, H2 : 2x1 mm
2
- AO, GND : 2x0,5 mm
- Door sensor : 2x0,5 mm
- RS 485 : 3x0,75 mm
works only with EC motor equipped curtains
it is recommended to connect the supply, using a conductor of the min. size
2 x 0,5 LIYCY
36
MU-WING-A
2m
1m
1,5m
C6/6kA
IDN=30mA type AC lub A
IN=16A
2
5x4,0mm
2
3x1,5mm
COMMENTS
2
LIYCY
2
LIYCY
2
LIYCY
2m
2