Power Options; Terminal Designations - Honeywell FocusPRO TH5000 Serie Guia De Instalacion

Ocultar thumbs Ver también para FocusPRO TH5000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Power options

Keep wires in this
shaded area
Wiring

Terminal designations

Shaded areas below apply only to
Conventional Terminals:
Rc
24VAC power from cooling
transformer
R
24VAC power from heating
transformer
W
Heat relay (stage 1)
W2 Heat relay (stage 2)
Y
Compressor contactor (stage 1)
Y2
Compressor contactor (stage 2)
G
Fan relay
C
24VAC common. For 2 transformer
systems, use common wire from
cooling transformer.
TH5110D
Rc
TH5220D
Y2
W2
G
W
TH5320U
Y2
W2
G
W
Remove factory-
installed jumper
only for two-
transformer
systems.
TH5320U/TH5220D
R
Y
C
W
G
C
Y
R
Rc
C
Y
R
Rc
FocusPRO
Insert batteries for primary
or backup power.
Connect
C
for primary AC power
(optional if batteries are installed).
or as otherwise noted.
Heat Pump Terminals:
Rc
24VAC power from cooling
transformer
R
24VAC power from heating
transformer
O/B Changeover valve
Y
Compressor contactor
Y2
Compressor contactor (stage 2)
-
only
TH5320U
G
Fan relay
Aux Auxiliary heat relay*
E
Emergency heat relay*
L
Sends output when set to Em. Heat
C
24VAC common
*Aux and E terminals combined on
TH5110D
Rc
R
Y
C
O/B
G
TH5220D
O /
L
E
Aux
G
TH5320U
O /
L
Y2
Aux
G
E
3
TH5000 Series
®
M29370
TH5320U
only.
C
Y
R
Rc
B
C
Y
R
Rc
B
M29371
69-1922EFS—01

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Th5110dTh5220dTh5320u

Tabla de contenido