Indoor Unit
1-15/16" (50mm) or more
from walls (on both sides)
•
Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines
below.
•
For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200mm) or less.
Wall facing one side
More than 1-15/16 (50)
Side View
INSTALLATION DIAGRAM
Front panel
M4 x 12L
Air filter
Outdoor Unit
INSTALLATION OF THE OUTDOOR UNIT (09/12)
More than 3-15/16 (100)
47-1/4
(1200)
or less
2-3/16" (55mm) or more from ceiling
Service lid
n Opening service lid
Service lid is removeable.
n Opening method
1) Remove the service lid
screws.
2) Pull out the service lid
diagonally down in the
direction of the arrow.
3) Pull down.
Wall facing two sides
More than 1-15/16 (50)
Wall facing three sides
More than 1-15/16 (50)
1-6
Caulk pipe
hole gap
Cut thermal insulation pipe to an
with putty.
appropriate length and wrap it with
tape, making sure that no gap is left
in the insulation pipe's cut line.
Wrap the insulation pipe
with the finishing tape
from bottom to top.
More than
5-7/8 (150)
More than
3-15/16 (100)
More than 1-15/16 (50)
Top View
More than 5-15/16 (150)
More than 11-13/16 (300)
Top View
Unit : Inch (mm)