M
AINTENANCE AND SERVICING
Service precautions
WARNING: ELECTRIC SHOCK
Caution when performing service to inverter equipment
DANGER
Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
Make sure that the power supply is turned off before
performing the maintenance work. The heater of the
compressor may operate even in stop mode.
Please note that some sections of the electric component box
are extremely hot.
In order to prevent damage to the PCB, first eliminate static
electricity by touching a metal part (e.g. stop valve) with your
hand. Then pull out the connector.
After measuring the residual voltage, pull out the outdoor fan
connector.
Make sure you do not touch a conductive section.
The outdoor fan may rotate due to strong backblow wind,
causing the capacitor to charge. This may result in an electric
shock.
After maintenance, make sure the outdoor fan connector is
connected again. Otherwise, the unit may break down.
Play it safe!
Touch a metal part by hand (such as the stop valve) in
order to eliminate static electricity and to protect the PCB
before performing service.
Service mode operation
Refer to the service manual to carry out any service mode operation.
D
ISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
RRHQ0011~016BAV3 + RRLQ011~016BAV3+W1
Outdoor unit for air to water heat pump
4PW54248-1
U
NIT SPECIFICATIONS
Technical specifications
RRHQ_V3
Painted
Casing material
galvanised
steel
1170 x 900 x
Dimensions h x w x d (mm)
Weight
(kg)
Operation range
• cooling (min./max.)
(°C)
10/46
• heating (min./max.)
(°C)
–20/35
• domestic hot water
(°C)
–20/35
(min./max.)
Daphne
Refrigerant oil
FVC68D
Piping connection
• liquid
(mm)
• gas
(mm)
Electrical specifications
Phase
Frequency
(Hz)
Voltage range
• minimum
(V)
• maximum
(V)
RRLQ_V3
RRLQ_W1
Painted
galvanised steel
1345 x 900 x 320
320
103
108
110
10/46
–20/35
–20/35
Daphne FVC68D
9.52
9.52
15.9
15.9
V3
W1
1~
3N~
50
50
207
360
253
440
Installation manual
15