Safe Use Instructions – DanLoad 6000
(Part No. 3-9000-670) for more information on
CALMON.
18.
Perform meter proofs to determine a meter
factor for DanLoad 6000 meter calibration for a
rack flow meter or master meter. Perform
calibration for a volume value of the meter prover.
Consult the flow measurement accounting
department of your organization before conducting
flow meter proofs.
In Program Mode, the Weights & Measures switch
must be set to on. Enter the Setup Mode and enter
the dynamic data codes, blending recipes for
proving, and factors and components. Verify the
values. Refer to Section 5 of the DanLoad 6000
Reference Manual (Part No. 3-9000-670) for more
information on specific proving methods.
19.
The DanLoad 6000 unit may now be put into
Operating (Loading) Mode, which is program code
025. Using program code 343 you can select
whether the unit uses Auto or Manual operating
mode. Auto mode provides remote control
operation, by communicating with a terminal
automation system and locally validating
configured safety circuits. In Manual mode the unit
communicates status to a terminal automation
system, but without remote control functions. In
Manual mode, the unit also performs local
validation of configured safety circuits.
20.
The DanLoad 6000 provides several means
of troubleshooting/diagnosis. Colored LEDs on the
display panel indicate: (Yellow) Auto Mode
On/Off/Flashing, (Green) Permissive Power
On/Off, and (Red) Alarm Status On/Off/Flashing.
Diagnostic tests are available in Program Mode.
Crash Memory logs are automatically generated if
a processor memory error is detected. For specific
information on conducting diagnostics or
troubleshooting, refer to Section 4 of the DanLoad
6000 Reference Manual (Part No. 3-9000-670).
If these methods do not solve the problem, contact
your local sales representative.
If you are experiencing problems that appear to be
hardware-related, return product to:
Emerson Process Management
Remote Automation Solutions
Outgang Lane
Pickering, North Yorkshire UK Y018 7JA
21.
To remove the DanLoad 6000 unit from
service, disconnect all power from the unit. Then
disconnect all wiring to and from the unit. Do not
forget to remove the grounding connections. Then
remove the enclosure from the mounting brackets.
Form A6151
Page 4