Technical Characteristics - Watts BT-M6Z02-RF 230V Guia Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
1 USER GUIDE
The Connecting box BT-M6Z02-RF is especially designed to control your Under Floor Heating and Cooling
system.
It can handle Normally Closed or Normally Opened actuators.
Connecting box has by conception 6 outputs actuators and this number can be extended to 10 or 12 with an
extension.
BT-M6Z02-RF works with thermostats linked in RF; it can have up to 12 thermostats linked to it and handle 12
independent regulations in parallel.
It works with all thermostats of BT02 RFand BT03 RF range.
Special features of BT-M6Z02-RFare:
-
pump or boiler output (wired or wireless with BT-WR02-RF or BT-WR02 FC RF)
-
Humidity management (via BT-D02-RF RH and BT-DP02-RF RH)
-
Heat and Cool signal input management (via BT-HCM02-RF)
-
Dehumidifer output (via BT-HCM02-RF)
-
Connection with BT-CT02-RF central unit

2 TECHNICAL CHARACTERISTICS

Operating Temperature
Regulation
characteristics
Supply Voltage
Outputs:
Pump or accessories
Actuators
Radio Frequency
CE Directives
Your product has been
designed in conformity
with the European
Directives.
Protection
Compatibility
BT-M6Z02-RF 230V
Proportional Integral regulation or Hysteresis regulation. Regulation is defined
by thermostat linked to channel (see thermostat leaflet)
230VAC +- 10% 50Hz
Relay => 5A / 250VAC (Free
contact)
Relay => 5A / 230 VAC ( L, N)
For easy installation we
recommend a maximum of 4
actuators by zones.
868, 3 MHz, <10mW.
Range of approximately 180 meters in open space.
Range of approximately 50 meters in residential environment.
Directive on General Products Safety 2001/95/EC
With BT S4Z02 RF: 10 Zones => 1 Master 6 + 1 Slave 4 zones
With BT S6Z02 RF: 12 Zones => 1 Master 6 + 1 Slave 6 zones
BT-WR02-RF, BT-WR02 FC RF
BT-D02 RF, BT-D02 RH RF
BT-DP02 RF, BT-DP02 RH RF
2
BT-M6Z02-RF 24V
0°C to 50°C
24Vac +- 10% 50Hz
Relay => 5A / 250Vac (free contact)
Triac => 3A / 24Vac
Total number of actuators is limited by
transformer (60VA) and fuse (2,5A)
and power of actuators.
R&TTE 2014/53/EU
LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
IP 30
BT-HCM02 RF
BT-PR02-RF
BT-FR02-RF
BT-CT02-RF
Repeater RF
BT-A02 RF
BT-D03 RF

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bt-m6z02-rf 24v

Tabla de contenido