DIAGRAM SHOWING REMOTE INSTALLATION OF THE MAINTENANCE BYPASS ON THE THREE PHASE –
SINGLE PHASE MODEL WITH SEPARATE BYPASS
Peripheral electric control panel
UPS internal connections
magneto-thermal switch compliant with the indications given in the "External Protection
LINE switch:
Devices" section.
NOTE: For installation with single phase input, use a bi-polar
INPUT switch: switch compliant with the indications given in the "UPS Internal Protections" section.
NOTE: For installation with single phase input, use a bi-polar disconnecting switch
OUTPUT switch: switch compliant with the indications given in the "UPS Internal Protections" section.
SERVICE BYPASS switch: disconnecting switch compliant with the indications given in the "UPS Internal
Protections" section, complete with auxiliary contact that is normally closed
LINE BYPASS switch: magneto-thermal switch compliant with the indications given in the "UPS External
protection devices" section
BYPASS INPUT switch: switch compliant with the indications given in "UPS Internal Protections" section
magneto-thermal switch