Nº:
I_60900215_EN_ES_FR
F05
Low battery alarm On (Volts). When the battery voltage has fallen below this value, the alarm relay will be
activated.
Default : 10.5V
F06
Low battery alarm Off (% SOC). When the State-of-charge percentage has risen above this value and the alarm
relay was activated, the alarm relay will deactivate again. When "FULL" is selected, the alarm relay is
deactivated when the Autosync parameters are met.
Default : 80%
F07
Peukert's exponent. The Peukert's exponent represents the effect of reducing battery capacity at higher
discharge rates. When the Peukert value of your battery is unknown, it is recommended to keep this value at
1.25. A value of 1.00 disables the Peukert compensation and could be used for Lithium based batteries.
Default : 1.25
F08
Shunt Amp Rating. This Function represents the Amp rating of your shunt at 50mV. Included with your battery
monitor is a 500Amp/50mV shunt, meaning that at 500A flowing through the shunt, a voltage of 50mV is
generated across the small 'Kelvin' screw terminals of the shunt. This voltage will be used by the battery monitor
to measure the amount of current.
Default : 500A
F09
Backlight mode. Represents the duration of backlight activation in seconds after key-press. The backlight can
also be set to be always "ON" or always "OFF". Function setting "AU", activates the backlight automatically
when charge / discharge current exceeds 1Amp or when a key is pressed.
Default : 30sec
F10
Alarm contact polarity. Enables selection between a normally open (NO) or normally closed (NC) contact.
Default : NO
F11
Auto-sync sensitivity. Only change this setting when F02 and F03 are set correctly and automatic synchronization
still . If automatic takes too long or does , lower this value. When the battery monitor synchronizes too early,
increase this value. fails synchronization never occur
Default : 5
F12
Firmware version. Displays the firmware version of the battery monitor (read only).
Default : x.xx
The last two Functions are socalled Reset Functions. By pressing the SETUP key the selected Reset Function can be
viewed. The default value for all Reset Functions is "OFF". To actually reset the selected Function, use the < and > keys
to change the value from "OFF" to "ON". Pressing the SETUP key again, will step back to the Setup menu. All reset
items set to "ON" will only be reset once the Normal Operating Mode is accessed again by pressing the SETUP key for
3 seconds. The following Reset Functions are available :
r.b
Reset Battery status. Use this reset item to reset your current battery status, for example after you have installed
a fresh battery of the same specifications as the previous one.
r.F
Reset Functions. This reset item can be used to reset all Function values to factory default values.
r.c
Reset zero-offset current. Use this reset item to remove small current readings on the display when no current is
flowing in- or out of the battery. When performing this reset action, please be 100% sure that all DC
consumers/chargers are disconnected or turned off.
Con el menú de configuración se puede ajustar el controlador de batería para que se adapte al sistema. Se puede
configurar una cantidad de parámetros, llamados funciones, para que se ajusten a unas determinadas necesidades.
Se puede acceder a este menú gracias a la secuencia siguiente:
Solé Diesel © 2012. www.solediesel.com.
The images, text and information contained in this manual are based on the product's features at the time of publication. Solé Diesel reserves the right to modify this document without prior notice. Las
imágenes, texto e información contenida en este manual se basan en las características del producto en el momento de la publicación. Solé Diesel se reserva el derecho de modificar el documento
sin previa notificación.
I_60900215_En_Es_Fr
Subject – Asunto:
Automatic battery charger kit v2 - Kit cargador de batería automático v2
Range : 8.0 - 33.0V
Step size : 0.1V
Range : 1 - 100% / FULL
Step size : 1%
Range : 1.00 - 1.50
Step size : 0.01
Range : 10 - 900A
Step size : variable
Range : OFF / 5...300 / ON / AU
Range : NO / NC
Range : 0 – 10 Step size : 1
Step size : variable