Sensor configuration
Configure and calibrate the fuel level sensor
1. Press the MENU button and select SENSOR
CONFIG.
2. Use Engine 1 connector or Engine 2
connector to select the connector to which the
sensor is connected.
3. Select the input connected to the sensor (i.e.
Resistive pin 8): "Off" appears to indicate that
no sensor is linked to the input or was disabled.
4. Select Fuel: Show value as and Calibration
parameters appear.
5. Select Show value as, then select the ID to be
assigned to the tank connected to the sensor.
6. Select Calibration to open calibration options.
7. Select Tank volume, to set tank capacity.
8. Select Sensor type, then select the sensor
type.
9. Select Calibration, then select the one or
three point calibration procedure (Do 1 point
cal/Do 3 point cal): calibration instructions
and the ohm value read in real-time by the
sensor [A] appear.
10. Empty the tank and wait for the read value to
stabilize. Then confirm by pressing ENTER.
11. For three point calibration, follow the on-screen
instructions.
12. Hold down the MENU button to return to the
data pages.