C
HECKING THE EQUIPMENT
Check the UPS carefully. If the UPS has been damaged during transit, keep the box and the packaging. Let the
carrier and the supplier know immediately.
P
LACING THE UPS
This UPS must have an adequate airflow. It must be placed in a clean indoor environment with no humidity,
away from flammable liquids and direct sunlight. A space of at least 4" / 100 mm must be left around the UPS.
The ambient temperature must be between 0°C and 40°C (32°F and 104°F), and the humidity level during
operation must be between 20% and 80% (without condensation).
Warning: A long period of use in an environment with a temperature over 25°C will shorten battery life. The UPS
should be placed at least 20 cm away from a monitor in order to avoid interference.
I
NSTALLING THE
The Dialog Vision family comprises: DVT models designed for vertical installation and the DVR models which
must be installed in 19" rack cabinets. The DVD models can be positioned vertically (using the supports) or
installed in 19" rack cabinets.
V
ERTICAL INSTALLATION OF THE
The DVD models are provided with supports to stabilise the UPS when it is positioned vertically.
1. Assemble the supports as shown in the figure.
2. Put the UPS in a vertical position and place the supports close to it. Carefully insert the UPS in the two
supports.
UPS
DVD
MODELS
I
NSTALLATION
45