MODEL
VA
NOMINAL
POWER
Watt
Nominal voltage
INPUT
Voltage range
Frequency
Voltage stability ( in battery
mode)
Frequency
OUTPUT
Frequency stability (in mains
mode)
Waveform
From mains power
OVERLOAD
From battery power
TRANSFER
Typical
TIME
Nominal battery voltage
BATTERY
Recharge time
UPS
DIMENSIONS
Battery box
Work environment
ENVIRONMENT
Noise
RS-232
USB
INTERFACE
Expansion slot
EPO
OTHER
Protection devices
DVT 500
500
350
(2)
(2)
12V
Dimensions
(LxHxD) mm
Weight (kg)
7
Excessive battery discharging – overcurrent – short-circuit – overvoltage – undervoltage –
Dialog Vision Tower
DVT 800
DVT 1100
800
540
230VAC
160VAC ± 3%
294VAC ± 3%
50/60Hz Automatic selection
230V +5%, -10%
50/60Hz Automatic selection (As selected for the input)
±0.1Hz
Sinusoidal
>110% alarm and failure after 3 minutes
>150% failure after 5 cycles
>110 % alarm and failure after 30 seconds
>120% failure after 5 cycles
4-msec. (6-msec.max.)
24V
Less than 6 hours at 90%
110X240X395
9
Not available
0- 40°C, from 20 to 80% relative humidity (without condensation)
Less than 50dBA
Not available
overheating
S
PECIFICATIONS
DVT 1500
1100
1500
740
1050
(1)
(1)
24V
48V
160X240X435
9
16
Yes
Yes
Yes
DVT 2000
2000
1350
48V
16
65