1.3

Transport and storage

• Ambient temperature: -25 ... 55 °C
• Relative humidity: 5 ... 95%, no water condensation
• Store product in its original package in dust-free room.
• Avoid high temperatures.
• After one year of storage, connect the device to mains voltage for 60 minutes.
1.4

After unpacking

• Check if the delivered devices corresponds to the order.
• Check the device for transport damage and completeness.
• Any defects/damage must be reported to the supplier immediately.
1.5

Place of installation

• In rooms without weather exposure.
• Avoid direct insolation.
• Avoid dust.
• Not in the neighborhood of strong electromagnetic fields.
• Not in the neighborhood of inflammable material.
• Provide for sufficient cooling. Install a fan if the frequency inverter is installed in a closed electrical cabinet.
• Altitude of installation: ≤ 4000 m, above 1000 m with reduced power (reduced output current).
• Ingress protection rating of frequency inverter: IP20.
1.6

Operating conditions

• Ambient temperature: 0...55°C, as from 40°C, power reduction should be considered.
• Relative humidity: max. 85%, no water condensation.
• Ambient pressure: 70 ... 106 kPa to be checked
• The frequency inverter may be operated in TN-, TT and IT mains.
Operation in corner-grounded TN systems is not allowed.
• The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more
frequently, it may be damaged. This must be considered when operating a mains contactor in jog operation
mode.
• Maximum permissible, prospective short circuit current at the grid connection:
up to 132 kW device power (size 7): 5 kA;
above 160 kW device power (size 8): ≥ 30 kA