Start-up procedure

The optional KP500 control unit is a practical tool for controlling the frequency inverter and setting and displaying
the frequency inverter parameters. This unit is attached to the front of the frequency inverter.
Other ways of commissioning (e.g. by means of optional communication modules) are described in
the co-applicable Operating Instructions.
5.1

Guided commissioning

NOTE
The frequency inverter may be connected to power supply every 60 s. If the unit is switched on more frequently,
it may be damaged. This must be considered when operating a mains contactor in jog operation mode.
Disable release of frequency inverter; there may be no signals at inputs STOA (digital input S1IND/terminal
X210A.3) and STOB (digital input S7IND/terminal X210B.2).
Turn mains voltage on.
The frequency inverter will perform a self-test.
Before the start of guided commissioning, the motor should not have been operated, as a part of the
machine data is dependent upon the operating temperature.
If the unit is in "as-delivered" condition or after resetting the unit to the factory settings, "SetUP"
will be displayed automatically for guided commissioning. After successful commissioning, you
can select the CTRL sub-menu in the main menu and use the function again.
Use the ENT key to switch to the CTRL sub-menu.
In the CTRL sub-menu, select the menu item "SetUP" and confirm by pressing the ENT key.
Use the ENT key to select parameter Configuration 30.
ENT
Use the arrow keys to enter the number 110 or 410.
110: sensor-less regulation according to U/f characteristic
410: sensor-less field-oriented control
ENT
If the setup was changed, the "SEtUP" message will be displayed again.
Confirm this message by pressing the ENT key in order to continue the commissioning procedure.
After initialization, confirm the selected configuration by pressing the ENT key.
Select the connected machine via parameter
NOTE
If the motor Type is not entered correctly, the drive may be damaged.

Operation mode

Unknown
0 -
Asynchronous
1 -
2 -
Synchronous
Reluctance
3 -
10 -
Transformer
02/15
369.
Motor Type
The motor is not a standard Type.
Three-phase asynchronous motor, squirrel cage
Three-phase synchronous motor
Three-phase reluctance motor
Transformer with three primary windings
Quick Start Guide ACU
Function
GB
63