Panel Mounting
Mini Panel
Front View
PELV (Class
2: USA)
wiring to
controls
Load
Feed
wiring
wiring
(bottom
(bottom
or side
or side
entry)
entry)
Wiring raceway
Mounting Guidelines
• For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
• Panel generates heat. Mount where ambient
temperature is 32-104 ºF (0-40 ºC).
• Relative humidity must be <90% non-condensing.
• Reinforce wall structure for panel weight and local
codes; see table.
• Mount panel where audible noise is acceptable
(internal relays click).
• Mount panel so line (mains) voltage wiring is at least 6
ft. (1.8 m) from audio or electronic equipment and
associated wiring.
• Mount within 7º of true vertical.
• Panel clearances are 12 in. (305 mm) above and
below and 0 in. to each side. Allow room for PELV
(Class 2: USA) clearance.
Warning! CE-marked panels with 10 A
circuit breakers are intended for industrial
or commercial use only.
Caution! This equipment is air-cooled.
Vents must not be blocked or you will
void the warranty.
R
Side View
12 in. (305
Feed
mm) min.
wiring
clearance
(top
entry)
Air flow
12 in. (305
mm) min.
Wall
Panel
Mini
GP3, GP4
Standard
GP8, LCP8
GP12, LCP12
GP16, LCP16
GP20, LCP20
GP24, LCP24
Large
GP36
GP48
GP60
GP72
GP144
*Packaging weight adds 150 lbs (69 kg) for large
Standard Panel
Front View
Wiring raceway
Load
wiring
(top
entry)
PELV (Class
2: USA)
wiring to
controls
12 in. (305 mm)
min. clearance
Max. Heat
BTUs
(Kcal)/Hour
685 (172.62)
1365 (343.98)
2045 (515.34)
2725 (686.70)
3405 (858.06)
4085 (1029.42)
4350 (1096.20)
5806 (1463.11)
7258 (1829.02)
8709 (2194.67)
17400 (4384.80)
panels, 50 lbs (23 kg) for medium panels, and 10
lbs (4.5 kg) for mini panels.
Installation Guide for Dimming Panels
Side View
12 in.
(305 mm)
min.
Air flow
Wall
Max. Weight w/o
Packaging*
pounds (kg)
30 (14)
115 (52)
120 (54)
145 (66)
160 (73)
175 (80)
325 (147)
550 (250)
600 (274)
650 (295)
1300 (590)
9