No: 24050 – 10/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: CI-200
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
C-200-U is BAA and TAA compliant (Product produced in the U.S.)
The CI-200 is a 24VDC Passive Infrared (PIR) occupancy sensor which controls lighting or HVAC systems based on occupancy and/or
ambient light levels in a given area.
PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them, so careful consideration must be given to sensor placement.
The CI-200 has a multi-cell, multi-tier Fresnel lens with a field of view of 360°. The sensor has two lens pattern options. The Extended
Range Lens will cover up to 1200 sq ft when mounted from 8-12 ft. The High Density/Reduced Range Lens will cover up to 500 sq ft
when mounted at 8-12ft.
Coverage shown in the diagrams below is maximum and represents coverage for half-step walking motion, with no barriers or obstacles
Top View @ 8ft
Extended Range Lens (Standard) CI-200
8 ft
2,4m
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
Side View
6,7 m
The effective coverage distances may be slightly less than the maximum sensing distance (see Coverage Patterns), depending upon
obstacles such as furniture or partitions, and this must be considered when planning the number of sensors and their positioning. See
the list for approximate coverage distances for different types of motion.
UNIT DESCRIPTION
COVERAGE PATTERNS
13 ft
7 ft
3 ft
0 3 ft
7 ft
13 ft
4m
2,1m
1m
1m
2,1m
4m
Wattstopper
360° Passive Infrared • Low Voltage Occupancy Sensor (version2)
IRP 360 ° • Détecteur de présence de basse tension (v2)
Pasivo infrarrojo de 360° • Voltaje bajo Sensor de ocupación (v2)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage ............................................... 20-30VDC (24VDC Typical)
Current Consumption .......................... @24VDC, 24mA Maximum
Isolated Relay Rating ............................... 1A @ 24VDC or 24VAC
Operating Temperature ........................ 32°F to 131°F (0° to 55°C)
Time Delay Adjustment ............................. 15 seconds-30 minutes
PIR Coverage
Model CI-200 ............................................................. up to 1200ft2
Model CI-200-1 ........................................................... up to 500 ft2
Light Level Adjustment ..................................................... 1-190FC
Sensitivity Adjustment .....................................Minimum-Maximum
UL & CUL Listed
Top View @ 8ft
High Density/Reduced Range Lens CI-200-1
22 ft
Side View
6,7 m
PLACEMENT
®
SPECIFICATIONS

Publicidad

loading

Resumen de contenidos para LEGRAND Wattstopper C-200-U

  • Página 1 Wattstopper ® 360° Passive Infrared • Low Voltage Occupancy Sensor (version2) IRP 360 ° • Détecteur de présence de basse tension (v2) Pasivo infrarrojo de 360° • Voltaje bajo Sensor de ocupación (v2) No: 24050 – 10/16 rev. 1 Installation Instructions • Instructions d’Installation • Instrucciones de Instalación Catalog Number •...
  • Página 2 Approximate coverage, for a mounting height of 8 feet: Lens option Walking motion Workstation (hand motion) Extended Range up to 22ft radius (1200 sq ft) 12ft radius (500 sq ft) High Density up to 12ft radius (500 sq ft) 9ft radius (300 sq ft) The CI-200 sensor can be mounted at various heights.
  • Página 3 WIRING DIRECTIONS Maximum CI-200s per power pack: B series = 5, BZ series = 7. When using more sensors than this, multiple power packs are required. For all configurations—connect the low voltage: • RED wire (+24VDC) from power pack to VIOLET wire on sensor. •...
  • Página 4 TROUBLESHOOTING Lights will not turn on: 1. Verify the lens is not masked in the direction being tested (see Masking). 2. Adjust Sensitivity settings up if needed (DIP switches #7 & 8). 3. Verify power pack and sensor connections are correct and secure. 4.
  • Página 5 INSTRUCTIONS EN FRANÇAIS DESCRIPTION SPÉCIFICATIONS Le CI-200 est un détecteur de présence infrarouge passif (IRP) Alimentation électrique ...20–30 V c.c. (24 V c.c. habituellement) 24 V c.c. qui contrôle l’éclairage ou les systèmes CVCA en Consommation de courant ....à 24 V c.c., 24 mA maximum fonction de la présence et / ou le niveau de luminosité...
  • Página 6 POSITIONNEMENT SUITE Pour les bureaux en espace ouvert avec des cloisons, il est préférable de placer les détecteurs au-dessus des intersections entre quatre postes de travail. Évitez également de placer les détecteurs près de conduits d’aération, car les courants d’air rapides ou les différences de température peuvent provoquer de fausses activations.
  • Página 7 INSTRUCTIONS DE CÂBLAGE Maximum CI-200s par les blocs d’alimentation de la série B = 5, série BZ = 7. Lorsque vous utilisez plus de 5 détecteurs, plusieurs blocs d’alimentation sont nécessaires. Pour raccorder les fils basse tension du bloc d’alimentation au détecteur : •...
  • Página 8 Mode de service Pour neutraliser toutes les fonctions du détecteur, réglez l’interrupteur DIP 6 sur ARRÊT. La DEL rouge s’allumera et restera allumée pendant toute la durée de la neutralisation. DÉPANNAGE Les lumières ne s’allument pas : 1. Vérifiez que la lentille n’est pas obstruée dans la direction testée (voir Obstruction). 2.
  • Página 9 INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN ESPECIFICACIONES El CI-200 es un sensor de ocupación con tecnología Suministro de voltaje ....20 a 30 V CC (24 V CC Típico) infrarroja pasiva (PIR) de 24 V CC que controla la Consumo de corriente ......@24 V CC, 24mA Máximo iluminación o sistemas HVAC basados en la ocupación y/o Especificaciones del relé...
  • Página 10 INSTALACIÓN Una caja de conexiones 4-S se puede usar con un marco empotrable de ADVERTENCIA: DESCONECTE LA 3”cuando los códigos de construcción locales obligan que las conexiones de ALIMENTACIÓN EN EL DISYUNTOR bajo voltaje estén contenidas en una caja de conexiones. ANTES DE INSTALAR EL SENSOR.
  • Página 11 Una carga de iluminación para control de ocupación, y una Blanco (neutro) segunda carga para ocupación y control de nivel de luz (luz ambiente): conecte: Carga de Rojo (línea) Fuente de alimentación Neutro Blanco • Cable AZUL desde fuente de alimentación al cable amarillo ilumina- ción del sensor.
  • Página 12 No. 24050 – 10/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/Wattstopper © Copyright 2016 Legrand Todos los derechos reservados.