Caldera de chapa de acero, alto rendimiento para combustibles líquidos o gaseosos, caldera homologada como baja temperatura según directiva 92/42 cee t mínima de retorno - 50 c (32 páginas)
Resumen de contenidos para Lamborghini Caloreclima PREX H 3 COND
Página 1
Caldera por condensación de altísimo rendimiento presurizada de acero Highly efficiency pressurized condensing boiler in steel Chaudière à condensation à très haut rendement pressurisée en acier PREX H 3 COND MAnuAle peR l’instAllAzione, l’uso e lA MAnutenzione MAnuAl de instAlACión, uso y MAnteniMiento instAllAtion, use And MAintenAnCe MAnuAl notiCe pouR l’instAllAtion, l’utilisAtion et l’entRetien...
CertifiCAzioni La marcatura CE certifica che i prodotti soddisfano i requisiti fondamentali delle direttive pertinenti in vigore. La dichiarazione di conformità può essere richiesta al produttore. CoDiCi iDentifiCAtivi Dei proDotti oil / gAS preX H 3 ConD 65 0RGZ3AXD preX H 3 ConD 100 0RGZ4AXD preX H 3 ConD 150 0RGZ5AXD preX H 3 ConD 230...
4.2 Principio di funzionamento Le caldaie PREX H 3 COND sono dotate di un focolare cilindrico cieco completamente bagnato nel quale si sviluppa il primo giro fumi, un tubo focolare di ritorno a grande diametro (2° giro) e da un fascio tubiero posto nella parte inferiore (3° giro). All’uscita dal fascio tubiero i fumi vengono raccolti nella camera fumo posteriore e da qui inviati al camino.
PREX H 3 COND 4.3 Dati tecnici - Dimensioni - Attacchi idraulici PREX H 3 COND 370 ÷ 650 PREX H 3 COND 65 ÷ 230 fig. 2 - Dimensioni e attacchi Legenda Pannello strumenti Fori per aggancio sollevamento Attacco scarico caldaia Flangia attacco bruciatore Mandata riscaldamento Attacco camino Portina di pulizia camera fumo...
Página 6
PREX H 3 COND 4.3.1 Tabella dati tecnici, dimensioni e attacchi Nella colonna a destra viene indicata l’abbreviazione utilizzata nella targhetta dati tecnici. preX H 3 ConD Categoria Gas i2H (IT - ES) Max. 61,3 94,3 141,5 217,0 349,1 471,7 613,2 Qn (Hi) Portata termica (kW) Min.
Página 7
PREX H 3 COND Scheda prodotto ErP MODELLO: PREX H 3 COND 65 (OIL) Marchio: LAMBORGHINI CALORECLIMA Caldaia a condensazione: SI Caldaia a bassa temperatura (**): NO Caldaia di tipo B1: SI Apparecchio di riscaldamento misto: NO Apparecchio di cogenerazione per il riscaldamento d'ambiente: NO...
Página 8
PREX H 3 COND Scheda prodotto ErP MODELLO: PREX H 3 COND 100 (OIL) Marchio: LAMBORGHINI CALORECLIMA Caldaia a condensazione: SI Caldaia a bassa temperatura (**): NO Caldaia di tipo B1: SI Apparecchio di riscaldamento misto: NO Apparecchio di cogenerazione per il riscaldamento d'ambiente: NO...
Página 9
PREX H 3 COND Scheda prodotto ErP MODELLO: PREX H 3 COND 150 (OIL) Marchio: LAMBORGHINI CALORECLIMA Caldaia a condensazione: SI Caldaia a bassa temperatura (**): NO Caldaia di tipo B1: SI Apparecchio di riscaldamento misto: NO Apparecchio di cogenerazione per il riscaldamento d'ambiente: NO...
Página 10
PREX H 3 COND Scheda prodotto ErP MODELLO: PREX H 3 COND 230 (OIL) Marchio: LAMBORGHINI CALORECLIMA Caldaia a condensazione: SI Caldaia a bassa temperatura (**): NO Caldaia di tipo B1: SI Apparecchio di riscaldamento misto: NO Apparecchio di cogenerazione per il riscaldamento d'ambiente: NO...
Página 11
PREX H 3 COND Scheda prodotto ErP MODELLO: PREX H 3 COND 370 (OIL) Marchio: LAMBORGHINI CALORECLIMA Caldaia a condensazione: SI Caldaia a bassa temperatura (**): NO Caldaia di tipo B1: SI Apparecchio di riscaldamento misto: NO Apparecchio di cogenerazione per il riscaldamento d'ambiente: NO...
5.2 Movimentazione Le caldaie PREX H 3 COND sono dotate di aggancio di sollevamento “A” (vedi fig. 5 e fig. 6). Porre attenzione alla movimentazione e avvalersi di attrezzatura idonea ai loro pesi. Prima di posizionare la caldaia togliere il basamento in legno svitando le viti di fissaggio (fig. 7).
5.3 Locale di installazione Le caldaie preX H 3 ConD vanno installate in locali ad uso esclusivo, rispondenti alle Norme Tecniche e alla Legislazione vigente e dotati di aperture di aerazione adeguatamente dimensionate. Le aperture di aerazione dovranno essere permanenti, comunicanti direttamente con l’esterno e posizionate a livello alto e basso in conformità...
5.5.1 Caratteristiche dell’acqua impianto Le caldaie preX H 3 ConD sono idonee all’installazione in sistemi di riscaldamento con ingresso di ossigeno non significativo (rif. sistemi “caso I” norma EN14868). In sistemi con immissione di ossigeno continua (ad es. impianti a pavimento senza tubi antidiffusione o a vaso aperto), oppure intermittente (ad es.
5.5.5 Tubazioni vaso espansione e valvola di sicurezza Le caldaie preX H 3 ConD sono adatte per funzionare con circolazione d’acqua forzata sia con vaso d’espansione aperto che chiuso. Un vaso di espansione è sempre necessario, per compensare l’aumento di volume dell’acqua dovuto al riscaldamento. Nel primo caso, l’altez- za della colonna idrostatica dovrà...
PREX H 3 COND 5.6 Porta anteriore apertura e regolazione Prendere nota della misura “X” di fig. 11 sui 4 angoli della porta. Svitare i 4 dadi “A” e controdadi “B” portandoli verso l’esterno fino a fine filetto. Fare attenzione a non far cadere la porta dalle svasature dei 4 dadi “A”.
PREX H 3 COND 5.7 Montaggio del bruciatore Il montaggio del bruciatore alla porta della caldaia, deve garantire una perfetta tenuta ai prodotti della combustione. Installato il bruciatore sulla caldaia, lo spazio tra il boccaglio del bruciatore e il materiale refrattario del portellone deve essere riempito con il materassino cera- mico (rif.
PREX H 3 COND 5.9 Posizionamento della sonda e dei bulbi Il pannello di controllo è dotato di una sonda di temperatura e tre bulbi. Sono presenti due pozzetti “A” e “B” vicino alla mandata riscaldamento “t1” (vedi fig. 17). È oBBligAtorio inserire nel pozzetto “A” (fig. 19) la sonda di temperatura “4” e il bulbo del termostato di sicurezza “3”.
PREX H 3 COND PANNELLO POrTASTruMENTI 6.1 Introduzione Il Pannello Comandi Termostatico deve essere destinato all’uso previsto da LAMBORGHINI che non è responsabile per danni causati a persone, animali o cose, da errori d’installazione, di regolazione, di manutenzione e da usi impropri.
PREX H 3 COND SChEMA DI PrINCIPIO - IMPIANTO PEr rISCALDAMENTO E PrODuZIONE DI ACQuA SANITArIA La scelta e l’installazione dei componenti dell’impianto è demandata per competenza all’installatore, che dovrà operare secondo le regole della buona tecnica e della Legislazione vigente. Gli impianti caricati con antigelo obbligano l’impiego di disconnettori idrici. Si ricorda che lo schema di fig.
PREX H 3 COND AvviAMento 9.1 Controlli preliminari Eseguiti i collegamenti idraulici, elettrici e del combustibile alla caldaia, prima dell’avviamento controllare che: • Il vaso di espansione e la valvola di sicurezza (se necessaria) siano collegati in maniera corretta e non siano in alcun modo intercettabili.
PREX H 3 COND 10.4 Pulizia della caldaia Gli accessori per la pulizia vengono forniti di serie e posizionati all’interno della camera di combustione. Per effettuare la pulizia procedere nel seguente modo (vedi fig. 25 e fig. 26): • Aprire il portello anteriore (rif. 1) ed estrarre i turbolatori (rif. 2).
PREX H 3 COND 10.6 verifica di funzionamento del bruciatore - Consultare il manuale d’istruzioni del bruciatore. - Seguire tutte le prescrizioni di norme locali in materia di manutenzione al bruciatore. 10.7 Possibili guasti e rimedi Di seguito una lista con le indicazioni dei principali guasti o anomalie che si possono verificare nella gestione della caldaia, con specificate le possibili cause e i relativi rimedi.
Página 28
PREX H 3 COND 1. Advertencias generales ................................29 2. Certificaciones ..................................29 3. Presentación ....................................30 4. Características técnicas, constructivas y dimensionales ..................... 30 Descripción del aparato ....................................30 Principio de funcionamiento ..................................30 Datos técnicos - Medidas - Conexiones hidráulicas ............................ 31 Identificación ........................................
El marcado CE acredita que los productos cumplen los requisitos fundamentales de las directivas aplicables. La declaración de conformidad puede solicitarse al fabricante. cÓdIgos de IdentIfIcAcIÓn de los Productos OIL / GAS PreX H 3 cond 65 0RGZ3AXD PreX H 3 cond 100 0RGZ4AXD PreX H 3 cond 150 0RGZ5AXD...
PresentAcIÓn Estimado Cliente: Gracias por elegir una caldera PreX H 3 cond. Este manual ha sido redactado para informarle sobre la instalación, el uso correcto y el mante- nimiento de la caldera, e incluye advertencias y consejos. Le rogamos leerlo atentamente y conservarlo con cuidado para cualquier consulta futura. Por su interés, le invitamos a seguir y observar con atención todas las instrucciones para aprovechar al máximo este producto de alta calidad.
PREX H 3 COND 4.3 Datos técnicos - Medidas - Conexiones hidráulicas PREX H 3 COND 370 ÷ 650 PREX H 3 COND 65 ÷ 230 fig. 2 - Medidas y conexiones Leyenda Panel de instrumentos Orificios para los ganchos de elevación Conexión descarga caldera Brida conexión quemador Ida calefacción Conexión chimenea...
Página 32
PREX H 3 COND 4.3.1 Tabla de datos técnicos, medidas y conexiones En la columna derecha se indica la abreviatura utilizada en la placa de datos técnicos. PreX H 3 cond Categoría Gas I2H (IT - ES) Máx. 61,3 94,3 141,5 217,0 349,1 471,7 613,2 Qn (Hi) Capacidad térmica (kW)
PREX H 3 COND Ficha del producto ErP MODELO: PREX H 3 COND 65 (OIL) Marca comercial: LAMBORGHINI CALORECLIMA Caldera de condensación: SÍ Caldera de baja temperatura (**): NO Caldera B1: SÍ Calefactor combinado: NO Aparato de calefacción de cogeneración: NO...
Página 34
PREX H 3 COND Ficha del producto ErP MODELO: PREX H 3 COND 100 (OIL) Marca comercial: LAMBORGHINI CALORECLIMA Caldera de condensación: SÍ Caldera de baja temperatura (**): NO Caldera B1: SÍ Calefactor combinado: NO Aparato de calefacción de cogeneración: NO...
Página 35
PREX H 3 COND Ficha del producto ErP MODELO: PREX H 3 COND 150 (OIL) Marca comercial: LAMBORGHINI CALORECLIMA Caldera de condensación: SÍ Caldera de baja temperatura (**): NO Caldera B1: SÍ Calefactor combinado: NO Aparato de calefacción de cogeneración: NO...
Página 36
PREX H 3 COND Ficha del producto ErP MODELO: PREX H 3 COND 230 (OIL) Marca comercial: LAMBORGHINI CALORECLIMA Caldera de condensación: SÍ Caldera de baja temperatura (**): NO Caldera B1: SÍ Calefactor combinado: NO Aparato de calefacción de cogeneración: NO...
Página 37
PREX H 3 COND Ficha del producto ErP MODELO: PREX H 3 COND 370 (OIL) Marca comercial: LAMBORGHINI CALORECLIMA Caldera de condensación: SÍ Caldera de baja temperatura (**): NO Caldera B1: SÍ Calefactor combinado: NO Aparato de calefacción de cogeneración: NO...
5.2 Desplazamiento Las calderas PREX H 3 COND están dotadas de gancho de elevación “A” (ver Fig. 5 y Fig. 6). Prestar atención al desplazamiento y utilizar equipos adecuados para el peso. Antes de emplazar la caldera, quitar la base de madera desenroscando los tornillos de fijación (Fig. 7).
5.3 Local de instalación Las calderas PreX H 3 cond se deben instalar en locales para uso exclusivo, conformes a las normas técnicas y a la legislación vigente, dotados de aberturas de aireación del tamaño adecuado. Las aberturas deben ser permanentes y estar comunicadas directamente con el exterior, a una altura conforme a las normas vigentes.
5.5.1 Características del agua de la instalación Las calderas PreX H 3 cond son idóneas para el montaje en sistemas de calefacción con baja entrada de oxígeno (ver sistemas “caso I” norma EN14868). En los sistemas con introducción de oxígeno continua (instalaciones de suelo sin tubos antidifusión o con depósito abierto) o intermitente (llenados frecuentes) se debe montar un separador físico (por ejemplo, un intercambiador de placas).
5.5.5 Tubos depósito de expansión y válvula de seguridad Las calderas PreX H 3 cond son adecuadas para funcionar con circulación de agua forzada con depósito de expansión abierto o cerrado. Un depósito de expansión siempre es necesario para compensar el aumento de volumen del agua debido al calentamiento. En el primer caso, la altura de la columna hidrostática debe ser de al menos 3 metros más que el revestimiento de la caldera y tener suficiente capacidad para...
PREX H 3 COND 5.6 Puerta delantera, apertura y regulación Tomar nota de la medida “X” de Fig. 11 en los 4 ángulos de la puerta. Desenroscar las 4 tuercas “A” y contratuercas “B” sacándolas hasta el fin de la rosca. Prestar atención para no dejar caer la puerta del abocardado de las 4 tuercas “A”.
PREX H 3 COND 5.7 Montaje del quemador El montaje del quemador en la puerta de la caldera debe garantizar una perfecta estanqueidad a los productos de combustión. Instalado el quemador en la caldera, el espacio entre la boca del quemador y el material refractario de la puerta se debe llenar con el colchón cerámico (ref.
PREX H 3 COND 5.9 Colocación de la sonda y los bulbos El panel de control está dotado de una sonda de temperatura y tres bulbos. Hay dos alojamientos, “A” y “B”, cerca de la ida de la calefacción “t1” (ver Fig. 17). es oBlIgAtorIo poner en el alojamiento “A” (Fig. 19) la sonda de temperatura “4” y el bulbo del termostato de seguridad “3”.
PREX H 3 COND PAnel de Instrumentos 6.1 Introducción El panel de mandos termostático se debe destinar al uso previsto por LAMBORGHINI, que no se hace responsable de daños a personas, ani- males o bienes, errores de instalación, regulación, mantenimiento o usos inadecuados.
PREX H 3 COND 6.5 Estructura El panel de mandos termostático está compuesto por: 1. Interruptor On/Off de encendido de la bomba de circulación (SA3) 2. Interruptor On/Off de encendido del quemador (SA2) 3. Interruptor On/Off de encendido de la caldera (SA1) 4.
PREX H 3 COND ESquEMA PRELIMINAR - INSTALACIóN PARA CALEfACCIóN y PRODuCCIóN DE AGuA SANITARIA La selección e instalación de los componentes corresponde al instalador, que debe operar según las reglas de la buena técnica y la legis- lación vigente. Las instalaciones cargadas con anticongelante exigen el empleo de desconectores hídricos. Se recuerda que el esquema de Fig.
PREX H 3 COND PuestA en mArcHA 9.1 Controles preliminares Realizadas las conexiones hidráulicas, eléctricas y del combustible a la caldera, antes de la puesta en marcha comprobar que: • El depósito de expansión y la válvula de seguridad (si es necesaria) estén conectados correctamente y no se puedan interceptar.
PREX H 3 COND 10.4 Limpieza de la caldera Los accesorios de limpieza se suministran de serie dentro de la cámara de combustión. Para la limpieza hay que proceder de la siguiente manera (ver Fig. 25 y Fig. 26): • Abrir la puerta delantera (ref. 1) y extraer los turboladores (ref. 2).
PREX H 3 COND 10.6 Verificación del funcionamiento del quemador - Consultar el manual de instrucciones del quemador. - Seguir todas las prescripciones de las normas locales en materia de mantenimiento del quemador. 10.7 Problemas y soluciones posibles A continuación se enumeran los principales problemas o anomalías que pueden ocurrir durante la gestión de la caldera, las causas posibles y las respectivas soluciones.
Página 54
PREX H 3 COND 1. General instructions ................................. 55 2. Certifications ..................................... 55 3. Introduction ....................................56 4. Technical, constructive and dimensional characteristics ..................... 56 Description of unit ......................................56 Working principle ......................................56 Technical data - Dimensions - Hydraulic connections ..........................57 Identification .........................................
The ce marking certifies that the products meet the essential requirements of the applicable directives. The declaration of conformity may be requested from the manufacturer. ProducT IdenTIfIcaTIon codeS oIl / GaS PreX H 3 cond 65 0RGZ3AXD PreX H 3 cond 100 0RGZ4AXD...
4.2 Working principle PREX H 3 COND boilers have a totally wet blind cylindrical firebox in which the first gas pass is developed, a larger firebox return tube (2nd pass) and a tube bundle at the bottom (3rd pass). At the tube bundle outlet the fumes are collected in the rear smoke chamber and conveyed to the flue.
PREX H 3 COND 4.3 Technical data - dimensions - Hydraulic connections PREX H 3 COND 370 ÷ 650 PREX H 3 COND 65 ÷ 230 fig. 2 - dimensions and connections legend Instrument panel Holes for lifting hook Boiler discharge connection...
Página 58
PREX H 3 COND 4.3.1 Table of technical data, dimensions and connections The column on the right gives the abbreviation used on the data plate. PreX H 3 cond Gas category I2H (IT - ES) Max. 61.3 94.3 141.5 217.0 349.1...
Página 59
PREX H 3 COND ErP product fiche MODEL: PREX H 3 COND 65 (OIL) Trademark: LAMBORGHINI CALORECLIMA Condensing boiler: YES Low-temperature boiler (**): NO B1 Boiler: YES Combination heater: NO Cogeneration space heater: NO Item Symbol Unit Value Seasonal space heating energy efficiency class (from A++ to G) Rated heat output η...
Página 60
PREX H 3 COND ErP product fiche MODEL: PREX H 3 COND 100 (OIL) Trademark: LAMBORGHINI CALORECLIMA Condensing boiler: YES Low-temperature boiler (**): NO B1 Boiler: YES Combination heater: NO Cogeneration space heater: NO Item Symbol Unit Value Rated heat output η...
Página 61
PREX H 3 COND ErP product fiche MODEL: PREX H 3 COND 150 (OIL) Trademark: LAMBORGHINI CALORECLIMA Condensing boiler: YES Low-temperature boiler (**): NO B1 Boiler: YES Combination heater: NO Cogeneration space heater: NO Item Symbol Unit Value Rated heat output η...
Página 62
PREX H 3 COND ErP product fiche MODEL: PREX H 3 COND 230 (OIL) Trademark: LAMBORGHINI CALORECLIMA Condensing boiler: YES Low-temperature boiler (**): NO B1 Boiler: YES Combination heater: NO Cogeneration space heater: NO Item Symbol Unit Value Rated heat output η...
Página 63
PREX H 3 COND ErP product fiche MODEL: PREX H 3 COND 370 (OIL) Trademark: LAMBORGHINI CALORECLIMA Condensing boiler: YES Low-temperature boiler (**): NO B1 Boiler: YES Combination heater: NO Cogeneration space heater: NO Item Symbol Unit Value Rated heat output η...
5.2 Handling PREX H 3 COND boilers have lifting hooks “a” (see Fig. 5 and Fig. 6). Be careful during handling, and use equipment suitable for the weight. Before positioning the boiler, remove the wooden base by undoing the fixing screws (Fig. 7).
5.3 Installation room PreX H 3 cond boilers must be installed in dedicated rooms, meeting the current Technical Standards and Legislation and equipped with adequate ventilation openings. The ventilation openings must be permanent, communicating directly with the outside and located at the top and bottom in accordance with current regulations.
5.5.1 System water characteristics PreX H 3 cond boilers are suitable for installation in heating systems with non-significant entry of oxygen (ref. systems "case I" EN14868). A separator (e.g. plate heat exchanger) must be provided in systems with continuous entry of oxygen (e.g. underfloor systems without antidif- fusion pipes), or intermittent (e.g.
5.5.5 Safety valve and expansion vessel pipes PreX H 3 cond boilers are suitable for operating with forced water circulation with open or closed expansion vessel. An expansion vessel is always necessary in order to compensate the increase in water volume due to heating. In the first case, the height of the hydrostatic column should be at least 3 meters above the boiler casing and be able to contain, between the free water surface in the vessel and the overflow pipe, the increase in volume of all the water in the system.
PREX H 3 COND 5.6 front door opening and adjustment Take note of the measurement “X” in Fig. 11 at the 4 corners of the door. Unscrew the 4 nuts “a” and locknuts “B” to near the end of the thread. Make sure the door does not fall off the flaring of the 4 nuts “a”.
PREX H 3 COND 5.7 Burner assembly Burner mounting on the boiler door must ensure perfect tightness to the combustion products. When the burner is installed on the boiler, the space between the burner nozzle and the refractory material of the door must be filled with the ceramic mat (ref. a - Fig. 15) supplied. This prevents overheating of the door which would otherwise become permanently deformed.
PREX H 3 COND 5.9 Probe and bulb positioning The control panel is equipped with a temperature probe and three bulbs. There are two wells “a” and “B” near the heating delivery “T1” (see Fig. 17). IT IS MandaTorY to insert in the well “a” (Fig. 19) the temperature probe “4” and the safety thermostat bulb “3”.
PREX H 3 COND InSTruMenT Panel 6.1 Introduction The Thermostatic Control Panel must be used as intended by LAMBORGHINI which is not responsible for any damage caused to people, animals or property due to incorrect installation, adjustment, maintenance and improper use.
PREX H 3 COND 7.2 Wiring diagram for burner and single-phase pump cod. 30902840 - Rev. 00 - 02/2018...
Página 75
PREX H 3 COND legend of wiring diagram Remote start enabling signal Boiler safety thermostat External safety enabling signal boiler flame thermostat Burner ON switch Digital thermometer Burner shutdown Second flame flame enabling signal Boiler water temperature probe Test thermostat button...
PREX H 3 COND ScHeMaTIc dIaGraM - SYSTeM for HeaTInG and doMeSTIc HoT WaTer The choice and installation of the system components is up to the installer, who must operate according to good practice and the current Legislation. Systems with antifreeze require the use of backflow preventers. Remember that the diagram in Fig. 24 is a schematic diagram.
PREX H 3 COND STarTuP 9.1 Preliminary checks After carrying out the plumbing, electrical and fuel connections to the boiler, before startup make sure: • The expansion vessel and the safety valve (if required) are properly connected and cannot be shut off in any way.
PREX H 3 COND 10.4 Boiler cleaning The cleaning accessories are supplied as standard and placed inside the combustion chamber. To carry out cleaning, proceed as follows (see Fig. 25 and Fig. 26): • Open the front door (ref. 1) and remove the turbulators (ref. 2).
PREX H 3 COND 10.6 Burner operation check - See the burner instruction manual. - Follow all the requirements of local regulations regarding burner maintenance. 10.7 Troubleshooting The following boiler troubleshooting guide gives the main faults or failures that may occur, with possible causes and cures.
Página 80
PREX H 3 COND 1. Précautions générales ................................81 2. Certifications ..................................... 81 3. Introduction ....................................82 4. Caractéristiques techniques, de construction et dimensionnelles ..................82 Descriptif de l'appareil ....................................82 Principe de fonctionnement ..................................82 Caractéristiques techniques - Dimensions - Raccords hydrauliques ......................83 Identification .........................................
« CE » atteste que les produits sont conformes aux exigences essentielles de l'ensemble des directives qui leurs sont applicables. la déclaration CE de conformité peut être demandée au fabricant. CoDES D'IDEntIfICAtIon DES ProDuItS gASoIl / gAZ PrEX H 3 ConD 65 0RGZ3AXD PrEX H 3 ConD 100 0RGZ4AXD PrEX H 3 ConD 150...
CArACtérIStIquES tECHnIquES, DE ConStruCtIon Et DImEnSIonnEllES 4.1 Descriptif de l'appareil Le type de construction des chaudières série PrEX H 3 ConD garantit une puissance et des rendements élevés avec rejet des fumées à basse température, d'où des émissions polluantes réduites.
PREX H 3 COND 4.3 Caractéristiques techniques - Dimensions - raccords hydrauliques PREX H 3 COND 370 ÷ 650 PREX H 3 COND 65 ÷ 230 fig. 2 - Dimensions et raccords légende Panneau d'instruments Trous pour oeillet de levage Raccord vidange chaudière...
Página 84
PREX H 3 COND 4.3.1 tableau caractéristiques techniques, dimensions et raccords La colonne de droite indique l'abréviation utilisée sur la plaquette des caractéristiques techniques. PrEX H 3 ConD Catégorie gaz I2H (IT - ES) Max. 61,3 94,3 141,5 217,0 349,1...
PREX H 3 COND Fiche de produit ErP MODÈLE: PREX H 3 COND 65 (OIL) Marque commerciale: LAMBORGHINI CALORECLIMA Chaudière à condensation: OUI Chaudière basse température (**): NO Chaudière de type B1: OUI Dispositif de chauffage mixte: NO Dispositif de chauffage des locaux par cogénération: NO Caractéristique...
Página 86
PREX H 3 COND Fiche de produit ErP MODÈLE: PREX H 3 COND 100 (OIL) Marque commerciale: LAMBORGHINI CALORECLIMA Chaudière à condensation: OUI Chaudière basse température (**): NO Chaudière de type B1: OUI Dispositif de chauffage mixte: NO Dispositif de chauffage des locaux par cogénération: NO Caractéristique...
Página 87
PREX H 3 COND Fiche de produit ErP MODÈLE: PREX H 3 COND 150 (OIL) Marque commerciale: LAMBORGHINI CALORECLIMA Chaudière à condensation: OUI Chaudière basse température (**): NO Chaudière de type B1: OUI Dispositif de chauffage mixte: NO Dispositif de chauffage des locaux par cogénération: NO Caractéristique...
Página 88
PREX H 3 COND Fiche de produit ErP MODÈLE: PREX H 3 COND 230 (OIL) Marque commerciale: LAMBORGHINI CALORECLIMA Chaudière à condensation: OUI Chaudière basse température (**): NO Chaudière de type B1: OUI Dispositif de chauffage mixte: NO Dispositif de chauffage des locaux par cogénération: NO Caractéristique...
Página 89
PREX H 3 COND Fiche de produit ErP MODÈLE: PREX H 3 COND 370 (OIL) Marque commerciale: LAMBORGHINI CALORECLIMA Chaudière à condensation: OUI Chaudière basse température (**): NO Chaudière de type B1: OUI Dispositif de chauffage mixte: NO Dispositif de chauffage des locaux par cogénération: NO Caractéristique...
InStAllAtIon 5.1 Emballage Les chaudières PREX H 3 COND sont livrées dans des caisses en bois contenant la porte, la boîte à fumée, l'isolation sur le corps et l'habillage. Le panneau d'instruments est livré en fonction du niveau d'équipement choisi par l'utilisateur.
5.3 local d'installation Les chaudières PrEX H 3 ConD doivent être installées dans des locaux à usage spécifique, répondant aux normes techniques et à la lé- gislation en vigueur et pourvus d'ouvertures d'aération adéquatement dimensionnées. Les ouvertures d'aération devront être permanentes, directement communicantes avec l'extérieur et positionnées aux niveaux haut et bas en conformité...
5.5.1 Caractéristiques de l'eau de l'installation Les chaudières PrEX H 3 ConD peuvent être installées sur des systèmes de chauffage sans apport significatif d'oxygène (réf. installations « de type I » selon la norme EN14868). En cas d'installations dotées d'amenée permanente d'oxygène (par exemple, plancher chauffant sans tuyaux pourvus d'une barrière anti-diffusion ou à...
Página 95
5.5.5 tuyauteries vase d'expansion et soupape de sûreté Les chaudières PrEX H 3 ConD sont prévues pour fonctionner à circulation d'eau forcée aussi bien avec le vase d'expansion ouvert que fermé. Un vase d'expansion doit toujours être monté pour compenser l'augmentation du volume de l'eau due au réchauffement. Dans le premier cas, la hauteur de la colonne hydrostatique devra être au moins équivalente à...
PREX H 3 COND 5.6 ouverture et réglage de la porte avant Mesurer la cote « X » indiquée en Fig. 11 sur les 4 angles de la porte. Dévisser les 4 écrous « A » et contre-écrous « B » en les amenant vers l'extérieur jusqu'à la fin du filet. Veiller à ne pas faire tomber la porte des décolletages des 4 écrous «...
PREX H 3 COND 5.7 montage du brûleur Le montage du brûleur sur la porte de la chaudière doit garantir une parfaite étanchéité aux produits de combustion. Après le montage du brûleur sur la chaudière, l'espace entre l'embout du brûleur et la matériau réfractaire de la porte doit être rempli avec le matelas céramique (rep.
PREX H 3 COND 5.9 Positionnement de la sonde et des bulbes Le tableau de commande est doté d'une sonde de température et de trois bulbes. Deux fourreaux « A » et « B » sont montés près du départ chauffage « t1 » (voir Fig. 17).
PREX H 3 COND PAnnEAu D'InStrumEntS 6.1 Introduction Le tableau de commande thermostatique doit être exclusivement destiné à l'usage prévu par LAMBORGHINI qui ne saurait être tenue pour res- ponsable des dommages aux personnes, animaux ou biens/choses causés par des erreurs dans l'installation, le réglage et l'entretien et/ou résultant d'usages impropres et inhabituels de l'appareil.
PREX H 3 COND 6.5 Structure Le tableau de commande thermostatique est composé des éléments suivants : 1. Interrupteur On/Off d'allumage du circulateur (SA3) 2. Interrupteur On/Off d'allumage du brûleur (SA2) 3. Interrupteur On/Off d'allumage de la chaudière (SA1) 4. Bouton-poussoir de test du brûleur (SB1) 5.
PREX H 3 COND SCHémA DE PrInCIPE - InStAllAtIon DE CHAuffAgE Et DE ProDuCtIon D'ECS Le choix et l'installation des composants de l'installation est confiée exclusivement à l'installateur, lequel devra opérer conformément aux textes réglementaires et règles de l'art en vigueur. Les installations chargées d'antigel nécessitent la mise en place de disconnecteurs hydrauliques.
PREX H 3 COND AllumAgE 9.1 Contrôles préliminaires Effectuer les raccordements hydrauliques, électriques et du combustible à la chaudière ; avant la mise en route, contrôler les points suivants : • Le vase d'expansion et la soupape de sûreté (si nécessaire) doivent être correctement connectés et ne doivent pouvoir être en aucun cas interceptés.
PREX H 3 COND 10.3 Entretien extraordinaire Entretien extraordinaire de fin de saison ou pour de longues périodes d'inutilisation. En plus d'effectuer les opérations décrites dans le chapitre précédent, il faudra : • Contrôler l'état d'usure des turbulateurs. • Ne pas vider l'installation et la chaudière.
PREX H 3 COND Après la mise en route, vérifier que l'appareil effectue d'abord un arrêt, puis le rallumage qui s'ensuit : • En modifiant le tarage du thermostat de la chaudière. • En agissant sur l'interrupteur principal du tableau de commande.
Página 108
Via Ritonda 78/a 37047 San Bonifacio - Verona - ITALY www.ferroli.com Fabbricato in Spagna - Fabricado en España Made in Spain - Fabriqué en Espagne...