Pressure Curves/Gas Delivery - Lamborghini Caloreclima EM 16/M-E Manual De Instrucciones

Ocultar thumbs Ver también para EM 16/M-E:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

PRESSURE CURVES/GAS DELIVERY

These curves show the gas pressure, in millibars, (at points Pi and Pt along the gas train) necessary to produce a given
delivery in m
3
/h. The pressures have been measured with the burner working and with a pressure of 0 mbar in the com-
bustion chamber. If the chamber is pressurized, the gas pressure necessary will be that given in the diagram plus that in
the combustion chamber.
Legend
1 Interception cock - airtight at 1 bar and pressure loss ≤
0.5 mbar.
2 Vibration-damping joint
3 Gas pressure point for pressure reading
4 Gas filter
5 Gas pressure regulator
6 Minimum gas pressure control device (pressure switch)
7 Class A solenoid safety valve. Closure time Tc ≤ 1".
8 Class A solenoid adjustment valve, with slow
EM 16/M-E
EM 26/M-E
BASIC
GAS TRAIN
9 Gas delivery regulator, normally incorporated in either
10 Combustion head.
11 Minimum air pressure control device
12 Maximum gas pressure (over 350 kW) control device (on
13 Tightness control device (on request)
Thermal output
Thermal output
- 31
-
opening or various stages and incorporated gas delivery
adjustment device. Closure time Tc ≤ 1".
solenoid valve 7 or 8.
request)
Legend
Pi Inlet pressure
(combustion head + gas train)
Pt Pressure at combustion head

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Em 26/m-e

Tabla de contenido