Temperature Unit
8
°C
Buzzer Status
9
Enabled
User Name
10
--------
Door Alarm Delay
11
60 min.
Relay contact
12
Norm.Close
MaxBlackoutTime
13
15 hours
Serial address
14
05
LO_Al HI_Al Del1
15
-50
+50
LO_Al HI_Al
16
-50
+50
New Password
17
0001
To scroll the different masks, the
the parameter to be modifi ed and with
disappears and the modifi cation of the parameter becomes operative.
Temperature unit of measure (°C, °F). Default °C.
Buzzer (Enabled, Disabled). Default Enabled.
Operator Name (responsable of the checking).
Door Alarm Delay. Default 60 min.
Relay Contact management (Disabled, norm. open, norm. closed). Default
Normally Closed.
Maximum selectable time (in hours) to signal a selectable blackout with a
longer duration. It can also be disabled. Default = 0 (disabled). If
the instrument will be switched off for a time exceeding this parameter, an
alarm is being started.
Identifi es the instrument in the serial communication.
HIGH and LOW temperature threshold of the probe 1 and respective alarm
DELAY. Default +50 °C of high temperature, -50 °C of low temp., 30 min of
20 min
delay.
HIGH and LOW temperature thresholds of the probe 2 and respective alarm
Del2
DELAY. Visible only when the second probe too is confi gurated. Default -
30 min
50°C of high temp., +50°C of low temp., 30 min of delay. To avoid erroneous
alarms, it is not possible to select high temperature thresholds lower than the
low temperature ones.
New password, to modify the one already existent. The "0000" value disables
the password.
buttons are usually being used. By pressing
its value is being increased/decreased. By pressing again
the cursor is being positioned on
the cursor