UPS Models
Dimensions and weight
W x D x H
Weight
Miscellaneous
Noise
Color
(6)
Ambient temperature
(1)
To maintain the output voltage within the range of precision indicated, it may have to be recalibrated after a long period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronized with the mains. If the frequency is outside the
tolerance limits or running on the battery, the frequency is the value selected +0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / mains @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically according to the capacity of the battery installed
(6)
20 – 25 °C for maximum battery life
(7)
@ 100% load & THDv ≤ 1%
R
L
EDUCING THE
OAD
If the output voltage is set to 115V and 110V (see "Configuring the UPS" paragraph), the maximum power output of the UPS is
reduced with respect to its rated value.
228 (Ph-Ph) ; 132 (Ph-N) = NO power output downgrading
220 (Ph-Ph) ; 127 (Ph-N) = NO power output downgrading
208 (Ph-Ph) ; 120 (Ph-N) = NO power output downgrading
199 (Ph-Ph) ; 115 (Ph-N) = 5% power output downgrading
190 (Ph-Ph) ; 110 (Ph-N) = 10% power output downgrading
(
115V
110V)
TO
AND
10 kVA
12 kVA
440 x 850 x 1320 mm
205 Kg
210 Kg
≤48dB(A)
15 kVA
247 Kg
≤52dB(A)
RAL 7016
0 – 40 °C
20 kVA
252 Kg