Festo AS-Interface ASI-EVA Serie Manual De Instrucciones página 26

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
Type
Load voltage connection (only when
configured by DIL-switch)
– Rated value (protected against
incorrect polarity)
– Residual ripple
– Max. current consumption
(sum current, at 24 V)
Outputs (valve connection)
– Voltage range
– Max. current consumption
– Without additional supply
– With additional supply
Digital inputs
– Max. current consumption
– per input
– sum current (all inputs)
– Input current high/low
– Logic level
– Reference potential
– Response delay
26
ASI-EVA ...
21.6 V ... 26.4 V DC
(24 V DC ±10%)
≤ 4 Vpp
Type ..-2E1A-.. Type ..-2E2A-..
0.5 A
0.5 A
(0.25 A per output)
Watchdog function active
after 50 ms (see 3.5)
Approx. 1.4 V under load volt-
age or AS-Interface voltage
2 * 1 W coil
0.5 A (0.25 A per output)
2 inputs based on standard
IEC 1131-2 type 2, 24 V DC,
PNP, Status display LED
Without
With
additional
additional
supply
supply
100 mA
200 mA
100 mA
200 mA
6 mA / 2 mA at 5V
(2-wire sensor)
ON:
11 V ...30 V
OFF: - 30 V ... 5 V
0 V
Typ. 3 ms (at 24 V)
Festo ASI-EVA... 0208a English

Publicidad

Tabla de contenido
loading