Electrical Wiring Connection - Daikin Siesta ATXB50CV1B Manual De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected
Indoor Unit
Terminal Block
1
2
SIG
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
All wires must be firmly connected.
Make sure all the wire do not touch the refrigerant pipings, compressor or any moving parts.
The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage.
The power supply cord must be equivalent to H07RN F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly fixed to avoid any gap.
Use round crimp style terminal for connecting wires to the power supply terminal block. Connect the wires by matching
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).
Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.
Downloaded from
www.Manualslib.com

ELECTRICAL WIRING CONNECTION

to comply with the local/national codes of regulations. This is also subject to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
Outdoor Unit
Interconnection
Terminal Block
cable
1
2
SIG
L
N
Power Supply Cable
Main
Fuse / Circuit
Switch
Breaker
Use the specified wire type
and connect it securely.
Attach insulation sleeve
Round crimp style terminal
Connect wires of the
same gauge to both side.
manuals search engine
Model
Voltage range**
Power supply cable size*
Number of Conductors
Interconnection cable size*
Number of Conductors
Recommended fuse/circuit breaker rating
* If the length of the cable is more than 2m, use cable with
bigger size.
Power
Supply
N / L2
L / L1
Firmly secure wire retainer so wire
terminations will not receive external stress.
Electric wire
Do not connect wires of the
same gauge to one side.
1 10
ATXB50/60CV1B
ARXB50/60CV1B
220 240V/~/50Hz + !
mm
2
2.5
3
mm
2
2.5
4
A
20
Power supply
terminal block
Shape wires so
that the service
lid and stop valve
cover fit securely.
Do not connect wires
of different gauges.