To change from "USER" mode (restricted access) to "INSTALLER" mode (all
settings), press both arrows on menu scroll button for 5 seconds.
Reverts to "USER" mode if no buttons are pressed for a period of 30 seconds.
No.
Description
Temperature:
Used to display the
temperature measured by the
p
sensor
10
Level:
Used to display the supply air
speed selected
d
l
t d
11
Time:
Used to set the time
Used to set the time
12
WINTER gradient (on water):
Used to set the gradient to
reach the WINTER mode
h th WINTER
setpoint
13
SUMMER gradient (on
water):
Used to set the gradient to
reach the SUMMER mode
14
setpoint
ECO differences:
Adjust the difference to the
setpoint using the comfort
mode
15
Unit
°C
Min.
0
y
Max.
51
Default
Increment
Unit
Min.
SPeedL
Max.
SPeedH
Default
Increment
Unit
hh.mm
Min.
00.00
Max.
23.59
Default
Increment
1 min
Unit
°C
Min.
1
d
Max.
15
Default
5
Increment
0.2
Unit
°C
Min
Min.
1
1
Max.
15
Default
8
Increment
0.2
Unit
°C
Min.
1
Max.
5
Default
3
Increment
0.5
VIII / INSTALLER SETTINGS:
Possible choices
Read-only
-
-
-
Read-only
-
-
Necessary for correct system operation when
parameter 01 is set to tIME.
-
The longer the gradient (near to 15°C), the more
gradually the heat exchange coils are supplied with
water. Drawback: reaching the temperature setpoint will
be very slow.
The shorter the gradient (near to 1°C), the more rapidly
the heat exchange coils are supplied with water.
Drawback: the system is similar to On/Off control.
Downward shift in WINTER mode:
Downward shift in WINTER mode:
e.g.: comfort setpoint 20°C, difference set at 3°C
ÎECO setpoint = 17°C
Upward shift in SUMMER mode:
e.g.: comfort setpoint 24°C, difference set at 3°C
ÎECO setpoint = 27°C
11