Energi Savr Node
Normal Operation
In normal operation, the following buttons allow the user to access
certain basic functions:
• (Raise)
– QSN-4T16-S and QSN-4T16-S-347: Raises zone light level in 1%
increments from 0–100%.
– QSN-4S16-S and QSN-4S16-S-347: Turns selected zone on.
• (Lower)
– QSN-4T16-S and QSN-4T16-S-347: Decreases zone light level in 1%
decrements from 100–0%.
– QSN-4S16-S and QSN-4S16-S-347: Turns selected zone off.
Note: On QSN-4T16-S and QSN-4T16-S-347: For any zone,
simultaneously pressing and holding the and buttons will toggle the
zone between high end and low end.
QS Link Input(s) Setup
seeTouch
QS wallstation or GRAFIK Eye
®
Scenes and Scenes + Off
Assigns a seeTouch
QS Wallstation or GRAFIK Eye
®
unit zone on the QS link.
1. To assign a seeTouch
QS Wallstation or GRAFIK Eye
®
unit, simultaneously press and hold the top and bottom buttons on the
wallstation or the top and bottom scene buttons on the GRAFIK Eye
unit for 3 seconds. The QS link enters Programming Mode. The sensor
LEDs on the ESN unit(s) will flash sequentially through each input and
group.
2. To assign or un-assign desired zone(s) to a wallstation, simultaneously
press and hold the the and buttons for the desired zone. A blinking
"Zone" LED indicates an assigned zone.
3. To exit Programming Mode, simultaneously press and hold the top and
bottom buttons on the wallstation or the top and bottom Scene buttons
on the GRAFIK Eye
QS unit for 3 seconds.
®
Note: For more advanced programming information, refer to the online
Programming Guide at:
www.lutron.com/Softswitchenergisavrnode
14 | Lutron
®
for 0 –10 V / Energi Savr Node
TM
QS unit:
®
QS unit to any ESN
®
QS unit to an ESN
®
with Softswitch
TM
Using LEDs to Troubleshoot
WARNING! Danger of Shock. May result in serious injury or
death. DO NOT WIRE WHEN LIVE! Switch off power to all power
feeds via circuit breaker before wiring or servicing the ESN unit.
Buttons and LEDs in the unit are used for programming and
troubleshooting. If line voltage shield is removed, the unit
must be accessed by a certified electrician, following local
codes.
LED
Occ
(Occupancy Sensor)
Photo
(Daylight Sensor)
IR
(Keypad or Infrared
Receiver)
Switch
QS
®
(IEC PELV / NEC
®
Class 2)
CCI
(Contact Closure
Input)
Emerg
(Emergency Contact
Closure Input)
QS Link
Wired
Zone
| Installation Guide
®
LED Behavior
Description
Continuous On
Sensor detects Vacancy
1 flash per second Sensor detects Occupancy
Off
Sensor never detected
Continuous On
Sensor is detected
Flashing
Sensor information transmitting
on the QS link
Off
Sensor never detected/sensor not
seeing light
Continuous On
Keypad or IR Receiver detected
Flashing
IR button press detected
Off
Keypad or IR Receiver never
detected
Continuous On
Switch detected/open
Flashing
Switch button press detected
Off
Switch never detected
Continuous On
Contact detected/open
Flashing
Contact closed
Off
Contact never detected
Continuous On
Normal operation/Contact Closed/
Jumpered
Rapid flash
Emergency Mode/Contact Open/
Jumper missing
On/Flashing
Device transmitting/receiving on
the QS link
3 quick flashes
Communication error
every 4 seconds
Off
Device not transmitting/receiving
on the QS link
Continuous On
Wired sensor
Continuous On
Load is on
Off
Load is off