Input Group Wiring - Lutron Electronics Energi Savr Node Guia De Instalacion

Ocultar thumbs Ver también para Energi Savr Node:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Energi Savr Node
Step-by-Step Installation Instructions
Step 4: Input Group Wiring
To connect a daylight sensor, occupancy sensor, infrared (IR) receiver, and/or IEC PELV / NEC
provided with the devices. Diagrams for the input terminals are shown below.
Note: The ESN unit accepts only one IR input (either daylight/IR sensor or IR receiver) per group.
Com: Common
Switch: IEC PELV / NEC
IR: IR Receiver*
Daylight: Daylight Sensor
Occ: Occupancy Sensor
20 V: 20 V-
Note: Maximum wire run length to each input not
to exceed 150 ft (46 m).
* Note: Only one IR device may be connected per input. If the IR signal from a daylight
sensor is connected, a wall control may not be connected to the same input, and
vice-versa.
** Connect the gray wire on -R model occupancy sensors.
English
for 0 –10 V / Energi Savr Node
TM
(continued)
Group 1 shown
Class 2
®
IR Transmitter
Daylight/IR Sensor*
Español
with Softswitch
TM
Class 2 dry-contact switch, refer to the instruction sheets
®
WARNING! Danger of Shock. May result in serious injury or death.
DO NOT WIRE WHEN LIVE! Switch off power to all power feeds via
circuit breaker before wiring or servicing the ESN unit.
Buttons and LEDs in the unit are used for programming and
troubleshooting. If line voltage shield is removed, the unit must be
accessed by a certified electrician, following local codes.
Note: There are four input groups;
each group has the same inputs as shown in the diagram below.

Input Group Wiring

• 20 to 12 AWG (0.5 to 4.0 mm
• Strip length: 1/4 in (6 mm)
• Torque: 5 in•lb (0.5 N•m)
Occupancy Sensor
IEC PELV / NEC
Dry-Contact Switch
Français
Português
| Installation Guide
®
2
)
Group 2 shown
Class 2
Wired Wallstation
®
or IR Receiver*
| 9
Lutron
®

Publicidad

Tabla de contenido
loading

Productos relacionados para Lutron Electronics Energi Savr Node

Tabla de contenido