powering a number of these devices. Please refer to the
chart below for details on how many devices the transformer
can support.
Greengate
Greengate
Greengate
PIR
Dual-Tech
Ultrasonic
Sensor
Sensor
Sensor
40
16
20
Please contact technical support if it is necessary to power
additional sensors beyond the numbers listed above.
These figures do not account for additional devices such
as lighted switches or digita switches being used. If using
a combination of devices, please contact technical support
for exact details on how many devices the logic panel can
power.
(Red Wire)
ON/IN
(White Wire)
ON/IN
+24 VDC
(Blue Wire)
(Red Wire)
Figure 11: Photosensor and Motion Sensor Wiring
Digital Switch Wiring
Each ControlKeeper 4A panel is capable of supporting up to
7 Digital Switch device stations and 1 GDS-I gateway device
(the number the controller is able to support is dependent on
the number of other low voltage devices wired that require
power from our logic board. Please contact Technical Support
for exact details of how many devices your logic board can
power.)
Digital Switch cable type should be Eaton's Cooper LC Cable,
Belden 1502R (non-plenum), or Belden 1502P (plenum).
For best network performance, one of the suggested cables
should be used. If the specified cable is not used and
communications problems occur that require troubleshooting
assistance, additional charges for support may be assessed.
ControlKeeper® 4A
PPS-4
PPS-5
Indoor
Outdoor
Photosensor
Photosensor
20
4
ON/IN
+24 VDC
Local Remote
(Blue Wire)
(Red Wire)
Jumpers in
Local Position
PPS4
Black
Yellow & White
Wires Not Used
+24 VDC
PPS5
Contact Input
Black
Photosensor
Wiring
Black
Typical Greengate
Motion Sensor Wiring
Digital Switches do not wire directly to the ControlKeeper 4A
panel, but are wired to a CAN Bus network that connects to
the ControlKeeper 4A through a GDS-I device. Digital Switch
devices should be networked together in a daisy chain
configuration. No T-Taps/Stars should be used.
The GDS-I device should reside somewhere within the
daisy chain switch network. Total daisy chain network length
should not exceed 1000 feet
The following instructions describe the GDS-I device
connection to the ControlKeeper 4A. Please refer to the
Digital Switch Installation Instructions for information on
wiring the Digital Switch network to the GDS-I device.
1.
Mount the GDS-I next to the ControlKeeper 4A panel.
A six foot phone style cable has been provided for
connection to the ControlKeeper 4A panel.
2.
Run a length of the Digital Switch LC or Belden cabling
from the GDS-I location to the low voltage section of
the ControlKeeper 4A.
3.
Connect the RED wire in the cable to the +V terminal
on the back of the GDS-I and to the ControlKeeper 4A
remote power connector +24 V terminals.
4.
Connect the BLACK wire in the cable to the GND
terminal on the back of the GDS-I and to the
ControlKeeper 4A remote power connector GND
terminal.
5.
Tape back or cap the blue and white wires and shield
wire for the cable. They will not be used for connection
between the GDS-I and lighting controller.
6.
Locate the 6 foot phone style cable included in the
GDS-I box. Run this from the GDS-I into the low voltage
section of the ControlKeeper 4A enclosure plugging the
end with 9 pin head into the GDS-I. Plug the end the
RJ11 phone style plug into the ControlKeeper 4A.
50-022510-02
ADDRESS
LED1
LED2
LED3
54-022510-
NETWORK
ALL OFF
ALL ON
1
2
3
4
5
6
7
8
Reset
J1
SW1
SW1
SW2
SW3
H1
CAN-RX
CAN-TX
LED4
LED5
J2
U1
U2
J3
U5
U6
L1 L2 L3 L4
J4
U7
TB1
PS1
U8
U9
J6
PCI-NET TERM
U10
U11
SC1
C29
REG1
REG2
REG3
U12
U16
U15
U13
U14
U17
U19
ANALOG INPUTS
DIMMING OUTPUTS
SWITCH INPUTS
TB3
TB4
TB5
AN AN AN AN
VIO
GRY
VIO
GRY
VIO
GRY
VIO
GRY
IN
IN
LS
IN
ANALOG COM
+24
+24
1
2
3
4
1
1
2
2
3
3
4
4
1
2
1
3
Wire Phone Style Cable to RJ11
Jack on CK4A and to GDS-1
BLACK Wire From GDS-1
GND to CK2 GND
RED Wire From GDS-1 V+
to CK2 +24 VDC
GDS-I
Cabling is EAton's Cooper LC Cable, Belden 1502R, or Belden 1502P
Figure 12: Digital Switch Gateway Wiring Detail
Digital Switch Wiring
J5
C20
LED6
RSC STAT
SR1
L1
S1
RESET PICS
LED7
SWIN STAT
SR2
POWER
C48
L2
U18
C40
C47
BR1
U20
TB7
TB6
TB2
LSO TEST
C49
J7
J8
LOCAL
IN
LS
IN
IN
LS
IN
IN
LS
C39
+24
+24
4
2
5
6
3
7
8
4
+24 GND
REMOTE
TP1
Local Remote Jumpers
Moved to Local Position
(Jumper Over Top Pins)
7