EN
11
Installation and commissioning
Fig. 9: detailed view DIP switches
If all DIP switches are in the OFF position (default setting), the following parameters are
active:
Address: 1
Baud rate: 19,200
Parity: Even
Termination: Disabled
Setting of the slave's address:
The slave address is set with the help of the 8-bit DIP switch "Address". If all switches
are in the OFF position, Address 1 is active. Address 0 is reserved for broadcast mes-
sages; addresses greater than 247 are not valid.
The coding of the address is binary. For the address 47, you must e.g. set the switches
1, 2, 3, 4 and 6 to ON.
Interface parameters:
The interface parameters are set with the help of the second 8-bit DIP switch. If the first
4 switches are in the OFF position, the transfer rate amounts to 19,200 bauds. If one of
these switches is set to ON, the corresponding baud rate is applicable.
Parity: If the two switches "ODD" and "NONE" are set to OFF, the parity is EVEN. Only
"ODD" or "NONE" activates the corresponding parity control.
Switch "Mobu EE": no function.
Switch "Term.": bus termination 124 ohms
2.2.5. Mounting the weather station
Close the housing by putting the cover back over the bottom part. The cover must snap
in on the left and right with a definite "click".
SHOWEAGPS Weather Station • Version: 28.10.2013 • Technical changes reserved. Errors reserved.