4.
The utility power outlet must be near the equipment and be eonduleurly accessible. To
isolate the UPS from AC input and swith it off, remove the plug from the utility power
outlet.
5.
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(earthed shockproof socket outlet) during operations since this would cancel the
protective earthing of the UPS system and of all connected loads.
6.
The UPS has its own internal power supply (battery). There is a risk that output sockets
may still be live after the UPS has been disconnected from the mains power supply.
7.
In an emergency situation, switch the UPS to the "Off" position and disconnect the unit
from the AC power supply.
8.
When the UPS is out of order, please refer to section: "trouble shooting" and call the
hot line.
9.
Equipotential earth bonding must be checked with external battery bank if any
Installation for UPS with terminal(s).
1.
An appropriate disconnect device as short-circuit backup protection should be provided
in the building wiring installation.
2.
An integral single emergency switching device which prevents further supply to the load
by the UPS in any mode of operation should be provided in the building wiring
installation according to local electrical laws.
3.
Connect the earth before connecting to the building wiring terminal.
4.
The EPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit.
This circuit must be separated from any hazardous voltage circuits by reinforced
insulation.
5.
Temperature Rating - Units are considered acceptable for use in a maximum ambient of
40°C (104°F).
Connected products:
1.
Combined UPS and connected equipment leakage current should not exceed 3,5 mA.
2.
Make sure that the connected load does not exceed UPS capabilities. To ensure
improved backup time and longer battery life, we recommend a load equivalent to 1/3 of
nominal power.
3.
Do not connect appliances or devices which would overload the UPS (e.g. big motor-
type equipment)) to the UPS output sockets or terminal.
4.
Do not plug the UPS input into its own output socket.
5.
Do not plug the UPS into a power strip or surge suppressor.
6.
The UPS has been designed for personal computers. It should not be used with
electrical or electronic equipment with inductive loads such as motors or fluorescent
lights.
7.
Do not connect any household appliances such as microwaves, vacuum cleaners, hair
dryers or life-support systems to the UPS.
8.
Due to excessive consumption, laser printers should not be connected to the UPS.
9.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
10. For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
and shall be easily accessible.
About batteries:
1.
It is recommended that a qualified technician change the battery.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
30
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 12 18 AA 59 205 19