SDE5-...
6.1 Setting the switching pressure on the SDE5-...-O/C-... :
1. Switch on the operating voltage.
2. Pressurize the SDE5-... with the desired
operating pressure (TP1).
3. Press the EDIT button 1 until the LED
flashes. When the button is released, the
SDE5-... saves the current operating pres-
sure (TP1) as the switching pressure (SP).
From this moment the SDE5-... operates
as designated.
Carry out a test run with various pressures
S
to ascertain whether the SDE5-... switches
as desired.
Mode 0:
Threshold
value
comparator
Fig. 15
Festo SDE-... 0204NH English
Switch element function NO
(normally-open)
OUT
1
Hy
SDE5- - ...- - O- - ...
0
SP = TP1
SDE5-...-O-...
SDE5-...-C-...
Fig. 14
Switch element function NC
(normally-closed)
OUT
1
Hy
SDE5- - ...- - C- - ...
P
0
SP = TP1
1
P
29