Installation
Attach Pump to Movable Section
1. For 1-1/4" discharge pipe using preassembled rail
sections, thread the supplied stainless steel pipe into
pump elbow and then reassemble the guide arm/
disconnect/check valve assembly to the pipe. tighten
assembly until pump is perpendicular to the guide
arm/disconnect.
2. For 1-1/4" discharge pipe using the cast iron base
elbow, thread pump adapter flange into pump elbow
fitting. Connect adapter flange to pull-out disconnect
using supplied yoke and bolts, making sure o-ring is
correctly positioned.
3. For 4" discharge pipe, bolt pump flange to cast iron
quick disconnect using poK-0400 hardware set.
Make sure the rubber gasket is correctly positioned
on the pump flange before tightening fasteners.
Attach Lift Chain/Cable
1. attach lifting chain bail with one end on the lifting
eye on pump and the other end on the guide plate
attachment point.
2. attach the lifting chain or cable to the bail with a
clevis, sliding the clevis along bail until the center of
gravity is found.
3. a hook is located on the upper rail support to hold
the upper end of the chain/cable when not in use.
repeat steps 1 and 2 for second pump, if duplex
operation is required.
4. position pump so the upper stand-off bracket
captivates both lift rails. If equipped, the lower
stand-off bracket must rest against both rails. slowly
lower the pump down the guide rails with the lift
chain/cable until the quick disconnect components
fully engage.
5. retain the power cord at the surface as pump is
lowered on the rails. do not lift or lower pump using
power cord. When pump is fully lowered, connect
power cord to control box, leaving a slight amount
of slack.
For parts or assistance, call Jung Pumpen Customer Service at 1-800-642-5930
Attach and Adjust Float Level Controls
the float level controls maintain the basin sewage level
by controlling pump turn-on and turn-off conditions.
attach level sensing float switches to bracket. General
rules to set level sensing heights are as follows:
1. the lower turn-off switch should be set so that the
pump stops when the fluid is approximately level
with the top of the pump. Consult the pump manual
for any settings below this point.
2. the upper turn-on switch should be set above the
lower turn-off switch. the exact height between the
two controls is determined by the number of pump
starts desired and depth of the basin. a maximum of
10 starts per hour should not be exceeded.
3. If equipped, the override switch is set at a specified
height above the upper turn-on control.
4. the alarm switch is set about 6" to 12" above the
override control.
5. no switch should be set above the inlet pipe.
5