2. ELECTRICAL CONNECTIONS

IMPORTANT
During installation, maintenance and cleaning, the appliance must not be powered.
The appliance must be powered only with 230 Vac voltage.
It is compulsory to install a multipolar switching device. The minimum separation distance between
contacts shall be at least 3 mm.
It is compulsory that the power supply circuit of the appliance is protected by a high sensitivity
differential protection device.
Do not insert metallic objects in or try to penetrate the plastic casing of the adjustment electronics.
If the power cable is damaged, it must be replaced only by a qualified electrician.

2.1. DETAILS ON INSTALLATION CONCERNING THE BATHROOM

Installation must be compliant with the standards and laws in force in the country of installation.
The radiator is in class II and with IP44 electrical protection. In the bathroom, it can be installed in areas
2 and 3 (see figure no.1) only if the control device cannot be touched by people that are using the
shower or the bath.
The radiator is equipped with class 2 electrical insulation, it must not be connected to the ground wire.
In the bathroom, protect the power line with a high sensitivity 30 mA differential
protection device
Install a multipolar switching device. The minimum separation distance between contacts shall
be at least 3 mm.
32
EN
fig. 1