4 Configuration

4.2.3 Quick wizard: Options

Domestic hot water settings
#
Code
[A.2.2.1]
[E-05]
Domestic hot water tank:
[A.2.2.3]
[E-07]
Tank booster heater:
[A.2.2.A]
[D-02]
Domestic hot water pump:
See also illustrations below.
Domestic hot water pump installed for...
Instant hot water
c
a
f
b
g
a Indoor unit
b Tank
c Domestic hot water pump
d Heater element
e Non-return valve
f Shower
g Cold water
Thermostats
#
Code
[A.2.2.4]
[C-05]
External room thermostat for the main
zone:
[A.2.2.5]
[C-06]
External room thermostat for the
additional zone:
Installation manual
12
Description
0 (No): NOT installed
1 (Yes): Installed
0 (Horizontal BSH): Installed at side
of the tank
1 (Backup heater): NOT installed
2: N/A
3: N/A
0 (No): NOT installed
1 (Secondary rtrn): Installed for
instant hot water
2
(Disinf.
shunt):
Installed
disinfection
Disinfection
c
a
d
b
e
Description
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only send
a thermo ON/OFF condition. No
separation
between
heating
cooling demand.
2 (C/H request): When the used
external room thermostat can send
a separate heating/cooling thermo
ON/OFF condition.
0: N/A
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only send
a thermo ON/OFF condition. No
separation
between
heating
cooling demand.
2 (C/H request): When the used
external room thermostat can send
a separate heating/cooling thermo
ON/OFF condition.
#
Code
[A.2.2.B]
[C-08]
Digital I/O PCB
#
Code
[A.2.2.6.1]
[C-02]
[A.2.2.6.2]
[D-07]
for
[A.2.2.6.3]
[C-09]
f
g
[A.2.2.6.4]
[F-04]
Alarm output logic
[C-09]
0 (default)
Closed output
1
Open output
Demand PCB
or
#
Code
[A.2.2.7]
[D-04]
or
Description
External sensor:
0 (No): NOT installed.
1 (Outdoor sensor): Connected to
PCB
measuring
the
temperature.
2 (Room sensor): NOT applicable.
Description
External backup heat source:
0 (No): None
1 (Bivalent): Gas, oil boiler
2: N/A
3: N/A
Solar pump station kit:
0 (No): NOT installed
1 (Yes): Installed
Alarm output on optional EKRP1HB
PCB:
0 (Normally open): The alarm
output will be powered when an
alarm occurs.
1 (Normally closed): The alarm
output will NOT be powered when
an alarm occurs. This installer
setting allows distinction between
detection
of
an
detection of a power failure to the
unit.
See also table below (Alarm output
logic).
Bottom plate heater
0 (No): NOT installed
1 (Yes): Installed
Alarm
No alarm
supply to unit
Open output
Open output
Closed output
Description
Demand PCB
Only applicable for RHBH/X04+08 and
RHVH/X04+08. Indicates if the optional
demand PCB is installed.
0 (No): NOT installed
1 (Yes): Installed
RHBH/X04+08+16CA
Rotex HPSU low temperature Bi-Bloc
4P330419-1A – 2012.11
outdoor
alarm
and
No power