6. START-UP

6.1. Leds check

The following table shows that status of the LEDs in relation to the
status of the inputs (the closed at rest automated system condition
is shown in bold).
Check the status of the signalling LEDs as per table below:
Tab. 1 - Operation of inputs status LEDs
LED
ON (closed contact)
STOP
Command disabled
OPEN A Command enabled
OPEN B Command enabled
BUS
See par. 7.2

6.2. Programming the Dips-switch

The settings of the DS1 dip-switch for programming the force and
the type of motor are shown in the following table.
Tab. 2 - DS1 programming (default settings in bold)
Dip-switch
LOW FORCE
MEDIUM - LOW FORCE
MEDIUM - HIGH FORCE
HIGH FORCE
COMPAS
DIABLO
MISTRAL 324 ENV
G-BAT 324 ENV / G-BAT 424 ENV
MISTRAL 324 / MISTRAL 324 LS
MISTRAL 424 / MISTRAL 424 LS
SIROCCO 2524 / SIROCCO 2524 LS
ELITE 324 / ELITE 424
G-BAT 324 / G-BAT 424
TRIGON 02-24
ROLLER 24
NOT USED
Before performing the Setup, select the operator con-
nected to the BRAIN 15 equipment with the DS3 and
DS4 dip-switches.
OFF (open contact)
Command enabled
Command disabled
Command disabled
Description
Guide for the installer

6.3. Time - setup learning

Before any manoeuvre is executed, a SETUP cycle must
first be run.
If the motor type is changed with the DS3 and DS4 dip-
switches after the SETUP, a new SETUP is requested.
When the board is powered up and a SETUP cycle has never been
executed, LEDs LD4 and LD5 begin to flash slowly to signal that
a SETUP cycle must be executed.
There are two possible types of SETUP: AUTOMATIC and MANUAL

6.3.1. AUTOMATIC SETUP

1.
Set the operators for manual operation and take them to
approx. half of the required opening.
2.
Lock the operators again and make sure that they cannot
be moved by hand.
3.
Press and hold down the SETUP key until the LEDs LD 4
and LD 5 light on a steady beam.
4.
Release the Setup key. The leaves start, one at a time,
the opening movement until they reach the mechanical
stop point.
If one or both leaves start moving with a closing mano-
euvre, cut power to the system and reverse the power
cables of the connected motor/motors. Supply power
to the system and resume from point 1.
5.
After having reached the opening stop point, the leaves
start, one at a time again, the closing phase until the gate
is completely closed.
6.
After a short pause the leaves start, one at a time, an opening
phase until they reach the mechanical stop point.
7.
When the opening position has been reached, the setup pha-
se is completed. If it has been performed correctly, the LEDs
LD4 and LD5 turn off. If this is not the case, the LEDs LD4
and LD5 flash and the setup procedure must be repeated.
With the AUTOMATIC SETUP procedure, the leaf delay
at closure and the pause time are set by default. To
change these values, a second level programming must
be executed (see paragraph 6.3.4.).

6.3.2. MANUAL SETUP

1.
Set the operators for manual operation and take them to
approx. half of the required opening.
2.
Lock the operators again and make sure that they cannot
be moved by hand.
3.
Press and hold down the SETUP key until the leaves start,
one at a time, an opening movement until they reach the
mechanical stop point.
If one or both leaves start moving with a closing mano-
euvre, cut power to the system and reverse the power
cables of the connected motor/motors. Supply power
to the system and resume from point 1.
4.
After having reached the opening stop point, the leaves
start, one at a time again, the closing phase until the gate
is completely closed.
5.
After a short pause, leaf 1 starts an opening phase.
6.
Send an OPEN command to determine the start of the
decelerated part and wait until the opening mechanical stop
point is reached.
7.
Leaf 2 starts the opening phase.
8.
Send an OPEN command to determine the start of the
decelerated part and wait until the opening mechanical stop
point is reached.
9.
When at rest, leaf 2 starts the pause time count. At the end
of the required time, send an OPEN command.
10. Leaf 2 starts the closing phase.
11. Send an OPEN command to determine the start of the
decelerated part and wait until the closing mechanical stop
point is reached.
12. Leaf 1 starts the closing phase.
BRAIN 15
Pagina 15