7.2.1

SoC alarm setting

When enabled, the alarm will activate when the state of charge falls below
the set value for more than 10 seconds. The alarm will deactivate when
the state of charge rises above the clear value
Default setting
Range
Disabled
Disabled /
enabled
When enabled
Default setting
Set value
1%
Clear value
2%

Low voltage alarm

7.2.2
When enabled, the alarm will activate when battery voltage falls below the set value for more than 10 seconds.
The alarm will deactivate when the battery voltage rises above the clear value.
Default setting
Range
Disabled
Disabled /
Enabled
When enabled
Default setting
Set value
1.0V
Clear value
1.1V

High voltage alarm

7.2.3
When enabled, the alarm will activate when battery voltage rises above the set value for more than 10 seconds.
The alarm will deactivate when the battery voltage drops below the clear value.
Default setting
Range
Disabled
Disabled /
enabled
When enabled
Default setting
Set value
1.1V
Clear value
1.0V
7.2.4

Low starter voltage alarm

This setting is only available if the Aux input has been set to "Starter battery".
When enabled, the alarm will activate when starter battery voltage falls below the set value for more than 10
seconds. The alarm will deactivate when the starter battery voltage rises above the clear value.
Default setting
Range
Disabled
Disabled /
Enabled
When enabled
Default setting
Set value
1.0V
Clear value
1.1V
22
0 – 100%
1%
0 – 100%
1%
0 - 95.0V
0.1V
0 - 95.0V
0.1V
0 - 95.0V
0.1V
0 - 95.0V
0.1V
0 - 95.0V
0.1V
0 - 95.0V
0.1V