Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visual inspections should be done at least once a month.
Access to transfer switch must not be obstructed. Keep
3 feet (92 cm) clearance around transfer switch. Check for
an accumulation of dirt, moisture and/or corrosion on and
around the enclosure, loose parts/hardware, cracks and/or
discoloration to insulation, and damaged or discolored
components.
Exercise the transfer switch at least once every three months
as described in the previous section "Testing the Automatic
Transfer Switch" unless a power outage occurs and Home
Generator System has gone through automatic sequence.
Allow generator to run for at least 30 minutes.
Contact a licensed electrical professional to inspect and clean
the inside of your transfer switch at least once a year.
10
Specifications
UL® 1008 Listed Transfer Switch
Model 071007
Maximum Load Current: . . . . . . . . . . . . . . . . . . . . 100 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Volts
Poles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50/60 Hz
Fault Current Rating . . 22,000 RMS Symmetrical Amperes*
Supervisory Contacts Rating:
A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Volt AC
B-B Terminals . . . . . . . . . . 1 Amp, 125 Volt AC, Pilot Duty
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 lbs.
* Short circuit rating is limited to the lowest capacity of any
device installed.