Troubleshooting

Problem
Automatic transfer switch does not
transfer to generator
Automatic transfer switch does not
transfer to utility
Generator is still running after switch
transfers to utility power
Generator is still running after utility
power is restored
10
Cause
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Utility disconnect circuit breaker
open.
2. Utility voltage not acceptable.
Engine cool down period.
1. Minimum engine run time has not
elapsed.
2. Fuse(s) in transfer switch is
defective.
Correction
1. Reset generator circuit breaker.
2. Refer to generator manual.
1. Reset utility disconnect circuit
breaker.
2. Wait for utility voltage to return to
normal.
Engine should stop after 1 minute.
1. Wait five minutes for transfer
switch to retransfer to utility power.
2. Check fuse(s) and replace if
necessary.